EasyManua.ls Logo

Emerson Rosemount 5300 Series - Confirm system readiness (HART only); Confirm HART revision capability; Confirm correct device driver; Switch HART revision mode

Emerson Rosemount 5300 Series
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2 Confirm system readiness (HART
®
only)
2.1 Confirm HART
®
revision capability
If using HART based control or asset management systems, confirm the HART
capability of those systems prior to transmitter installation. Not all systems
are capable of communicating with HART Revision 7 protocol.
Transmitters with a firmware version 2F0 or later can be configured for either
HART Revision 5 or 7.
2.2 Confirm correct device driver
Procedure
Verify that the latest Device Driver (DD/DTM
) is loaded on your systems
to ensure proper communication. See Table 2-1.
Download the latest Device Driver from Emerson.com/DeviceInstallKits.
Table 2-1: Rosemount 5300 Device Revisions and Files
Firmware version
(1)
Find Device Driver
HART
®
Universal
Revision
Device Revision
(2)
2F0 or later 7 4
5 3
2A2 - 2E0 5 3
(1) Firmware version is printed on the transmitter head label, e.g. SW 2E0 or can
be found in Rosemount Radar Master (select Device > Properties).
(2) Device revision is printed on the transmitter head label, e.g. HART Dev Rev 4.
2.3 Switch HART
®
revision mode
If the HART configuration tool is not capable of communicating with HART
Revision 7, the device will load a generic menu with limited capability. To
switch the HART revision mode from the generic menu:
Procedure
1. Locate the “Message” field.
2. In the Message field, enter HART5 or HART7 and then 27 trailing
spaces.
February 2019 Quick Start Guide
Quick Start Guide 5