Unidrive M100-101 Quick Start Guide 33
Issue Number: 6
Defines the behaviour of digital output 1.
For further information, refer to the Drive User Guide.
00.035 {08.091} DO1 Control (terminal 10)
RW Num US
OL
Ú
0-21
Ö
0
Value Description
0
User defined by Digital IO1 Source/Destination A, Digital IO2 Source/Destination A,
Relay 1 Output Source A, or Relay 2 Output Source A.
1 Drive running signal (RUN)
2 Frequency arrived signal (FAR)
3 Frequency level detection signal (FDT1)
4 Frequency level detection signal (FDT2)
5 Overload detection signal (OL)
6 Power off state (LU)
7 External fault stop (EXT)
8 Frequency upper limit (FHL)
9 Frequency lower limit (FLL)
10 Drive running at zero frequency
14 Drive (RDY)
15 Drive OK
18 Brake release
19 Torque limiting (Valid while the torque is limited by torque limiting value 1/2)
20 Forward or reverse
21 Motor 1 or 2
Unidrive M100 101 Quick Start Guide English Iss6.book Page 33 Wednesday, September 9, 2015 4:07 PM