32 SI-Ethernet User Guide
Issue: 1
5.10.7 Menu 20 - EtherNet/IP Setup
Table 5.11 Menu 20 parameters
15.011
Modbus Timeout
Event Destination
This slot (0),
Slot 1 (1),
Slot 2 (2),
Slot 3 (3),
Slot 4 (4)
This slot
(0)
RW Txt US
15
.012
Modbus Timeout
Event Type
No event (0),
Trigger Event (1),
Trigger Event 1 (2),
Trigger Event 2 (3),
Trigger Event 3 (4),
Trigger Event 4 (5)
No event
(0)
RW Txt US
15.013
Modbus Register
Addressing Mode
Standard (0),
Modified (1)
Standard
(0)
RW Txt US
15.020 Priority Connection 1
0.0.0.0 to
255.255.255.255
0.0.0.0 RW IP US
15.021 Priority Connection 2
0.0.0.0 to
255.255.255.255
0.0.0.0 RW IP US
15.022 Priority Connection 3
0.0.0.0 to
255.255.255.255
0.0.0.0 RW IP US
15.023
Priority Connection 4
0.0.0.0 to
255.255.255.255
0.0.0.0 RW IP US
Parameter Range Default Type
Parameter Range Default Type
20.001 Enable EtherNet/IP Off (0) or On
(1)
On
(1)
RW Bit US
20.002 Reset Off (0) or On
(1)
Off (0) RW Bit NC
20.003 Default Off (0) or On
(1)
Off (0) RW Bit NC
20.004 Configuration error
No error (0),
RPI event dst
(1),
RPI event type (2),
IDLE event dst
(3),
IDLE event type
(4),
Input mapping
(5),
Output mapping (6),
In
cons trig pr (7),
Out cons trig pr (8)
RO Txt ND NC PT
20.007
Cyclic data transfers
per second
0 to 65535
M
essag
es
/s
RO Num ND NC PT
20.011 RPI timeout action
Trip (0),
Send flt values (1),
Clear output (2),
Hold last (3),
No Action (4)
Hold last (3) RW Txt US
20.012
RPI timeout event
destination
This slot (0),
Slot 1 (1),
Slot 2 (2),
Slot 3 (3),
Slot 4 (4)
This slot (0) RW Txt US