Controls whether or not the module will attempt to use a Dynamic Host Configuration
Protocol (DHCP) server to obtain the IP address, subnet mask, default gateway and
DNS servers.
When DHCP is enabled, the following parameters will become read-only immediately
(no reset required):
• IP Address (S.02.006)
• Subnet Mask (S.02.007)
• Default Gateway (S.02.008)
• Primary DNS (S.02.009)
• Secondary DNS (S.02.010)
Controls and displays the IP address of the module.
If DHCP is enabled this parameter becomes read-only, and until an IP address is
allocated to the module will display 0.0.0.0.
If DHCP is disabled the module will initialize, on reset or power cycle, with the IP
address stored for the parameter.
S.02.005 DHCP Enable
Minimum 0 Maximum 1
Default 1 Units
Type 1 Bit User Save Update Rate Background read
Display Format None Decimal Places 0
Coding RW, BU
S.02.006 IP Address
Minimum
0
(Display: 0.0.0.0)
Maximum
4294967295
(Display:255.255.255.255)
Default
3232235876
(Display:192.168.1.100)
Units
Type 32 Bit User Save Update Rate
DHCP enabled: write on
event;
DHCP disabled: read on
reset
Display Format IP Address Decimal Places 0
Coding RW, BU