SI-Ethernet User Guide 65
Issue: 1
Safety
information
Introduction
Mechanical
installation
Electrical
installation
Getting started Parameters
Key features
and Protocols
PC Applications Security Diagnostics
Glossary of
terms
Index
This parameter is used to set the number of contiguous parameters for the Rx1 link.
This specifies the type of transmission for the Rx1 link.
This parameter specifies the watchdog timer for the Rx1 link. If no cyclic data is received
on the Rx1 link the action taken will be determined by the setting in Rx1 Timeout Action
(S.10.046).
S.10.043 Rx1 Parameter Count
Minimum 0 Maximum 10
Default 0 Units
Type 8 Bit User Save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, BU
S.10.044 Rx1 Source Type
Minimum 0 Maximum 5
Default 0 Units
Type 8 Bit User Save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, TE, BU
Value Text Description
0 Direct Link is unicast or broadcast
1 Multicast1 Link is multicast to the IP address
2 Multicast2 Link is multicast to the IP address
3 Multicast3 Link is multicast to the IP address
4 Multicast4 Link is multicast to the IP address
5 Local Link will receive from local transmit link
S.10.045 Rx1 Timeout
Minimum 0 Maximum 65535
Default 100 Units ms
Type 16 Bit User Save Update Rate Read on reset
Display Format None Decimal Places 0
Coding RW, BU
It is good system design to allow for some message loss by setting the timeout duration
to be greater than the transmit period by a factor of 2 or more.