Typical short term overload limits
The maximum percentage overload limit changes depending on the selected motor. Variations in 
motor rated current, motor power factor and motor leakage inductance all result in changes in the 
maximum possible overload. Typical values are shown in the table below:
Table 2-6 Typical overload limits
Generally the drive rated current is higher than the matching motor rated current allowing a higher 
level of overload than the default setting.
The time allowed in the overload region is proportionally reduced at very low output frequency on 
some drive ratings.
Output current
The continuous output current ratings given on the rating label are for maximum 40 °C (104 °F),  
1000 m altitude and 3 kHz switching frequency (except where shown). Derating is required for higher 
switching frequencies, ambient temperatures >40 °C (104 °F) and higher altitude. For derating 
information, refer to Chapter 5 Technical data on page 88
Input current
The input current is affected by the supply voltage and impedance. The input current given on the 
rating label is the typical input current and is stated for a balanced supply.
Operating mode RFC from cold RFC from 100 %
Open loop 
from cold
Open loop 
from 100 %
Normal Duty overload with motor rated 
current = drive rated current
110 % for 165 s 110 % for 9 s 110 % for 165 s 110 % for 9 s
Heavy Duty overload with motor rated 
current = drive rated current (size 8 and 
below)
200 % for 28 s 200 % for 3 s 150 % for 60 s 150 % for 7 s
Heavy Duty overload with motor rated 
current = drive rated current (size 9 and 10)
175 % for 42 s 175 % for 5 s 150 % for 60 s 150 % for 7 s
The maximum overload level which can be attained is independent of the speed. 