38 Unidrive M / HS Frame 7 to 10 Power Installation Guide
Issue Number: 5
Figure 3-16 View showing sealing clamps provided in through hole mounting kit
Table 3-4 Power losses from the front of the drive when through-panel mounted
For detailed information regarding high IP through panel mounting see section
3.4.3 Through-panel mounting on page 26.
When designing a high IP enclosure, consideration should be given to the dissipation from
the front of the drive.
Frame size Power loss
7 204 W
8 347 W
9A/9E/10E 480 W
Enclosure
rear wall
Sealing
brackets
NOTE
NOTE
Unidrive M frame7 to 10 Power Installation Guide issue5.book Page 38 Tuesday, May 24, 2016 11:52 AM