44 • XM679K I&O Manual 026-1218 Rev 4
ASr 1.0 Pr2
Differential for fan / offset for anti sweat
heater
[-45°F to 45°F]
[-25.5°C to 25.5°C]
PbA 5.0 Pr2 Proportional band for modulating output
[1°F to 45°F]
[0.1°C to 25.5°C]
AMi 0 Pr2 Minimum output for modulating output 0 to AMA
AMA 100 Pr2 Maximum output for modulating output AMi to 100
AMt 200 Pr2 Time with fan at maximum speed 0 to 255 s
ALARM
rAL P1 Pr1 Probe for temperature alarm
nP(0) - P1(1) - P2(2) - P3(3) - P4(4) -
P5(5) - tEr(6)
ALC Ab Pr1 Temperature alarm configuration rE(0) - Ab(1)
ALU 10 Pr1 High temperature alarm setting
[0°F to 90°F or ALL to 302°F]
[0.0°C to 50.0°C or ALL to 150.0°C]
ALL -30 Pr1 Low temperature alarm setting
[0°F to 90°F or -67°F to ALU°F]
[0.0°C to 50.0°C or -55.0°C to ALU]
AHy 1.0 Pr1 Differential for temperature alarm
[1°F to 45°F]
[0.1°C to 25.5°C]
ALd 15 Pr1 Temperature alarm delay 0 to 255 (min.)
dLU 150 Pr2
High temperature alarm setting
(defrost probe)
[0°F to 90°F or dLL to 302°F]
[0.0°C to 50.0°C or dLL to 150.0°C]
dLL -55 Pr2
Low temperature alarm setting
(defrost probe)
[0°F to 90°F or -67°F to dLU°F]
[0.0°C to 50.0°C or -55.0°C to dLU]
dAH 1.0 Pr2
Differential for temperature alarm
(defrost probe)
[1°F to 45°F]
[0.1°C to 25.5°C]
ddA 15 Pr2 Temperature alarm delay (defrost probe) 0 to 255 (min.)
FLU 150 Pr2
High temperature alarm setting
(fan probe)
[0°F to 90°F or FLL to 302°F]
[0.0°C to 50.0°C or FLL to 150.0°C]
FLL -55 Pr2
Low temperature alarm setting
(fan probe)
[0°F to 90°F or -67°F to FLU°F]
[0.0°C to 50.0°C or -55.0°C to FLU]
FAH 1.0 Pr2
Differential for temperature alarm
(fan probe)
[1°F to 45°F]
[0.1°C to 25.5°C]
FAd 15 Pr2 Temperature alarm delay (fan probe) 0 to 255 (min.)
dAo 1.3 Pr1 Delay of temperature alarm at start-up 0 to 24.0(144)(hours.10min)
EdA 30 Pr1 Alarm delay at the end of defrost 0 to 255 min
dot 15 Pr1
Temperature alarm exclusion after door
open
0 to 255 min
Sti nu Pr2 Stop regulation interval “nu”(0) to 24.0(144)(hour.10min)
Std 3 Pr2 Stop duration 1 to 255 min
oA6 AUS Pr2 Sixth relay output configuration
CPr(0) - dEF(1) - FAn(2) - ALr(3) -
LiG(4) - AUS(5) - db(6) - OnF(7)
oA7 ALr Pr2
Modulating output configuration
(if CoM=oA7)
CPr(0) - dEF(1) - FAn(2) - ALr(3) -
LiG(4) - AUS(5) - db(6) - OnF(7)
CoM Cur Pr2 Modulating output configuration
CUr(0) - tEn(1) - PM5(2) - PM6(3) -
oA7(4)
AOP cL Pr1 Alarm relay polarity OP(0) - CL(1)
iAU n Pr1
Auxiliary output independent from ON/
OFF state
n(0) – Y(1)
Table 23-1 - Default Setting Values (Continued)