MODBUS Termination Blocks Default Setting Values • 45
DIGITAL INPUTS
i1P cL Pr1 Digital input 1 polarity OP(0) - CL(1)
i1F dor Pr1 Digital input 1 configuration
EAL(0) - bAL(1) - PAL(2) - dor(3) -
dEF(4) - AUS(5) -LiG(6) - OnF(7) -
Htr(8) - FHU(9) - ES(10) - Hdy(11)
d1d 15 Pr1 Digital input 1 activation delay 0 to 255 (min.)
i2P cL Pr1 Digital input 2 polarity OP(0) - CL(1)
i2F LiG Pr1 Digital input 2 configuration
EAL(0) - bAL(1) - PAL(2) - dor(3) -
dEF(4) - AUS(5) -LiG(6) - OnF(7) -
Htr(8) - FHU(9) - ES(10) - Hdy(11)
d2d 5 Pr1 Digital input 2 activation delay 0 to 255 (min.)
i3P cL Pr1 Digital input 3 polarity OP(0) - CL(1)
i3F ES Pr1 Digital input 3 configuration
EAL(0) - bAL(1) - PAL(2) - dor(3) -
dEF(4) - AUS(5) -LiG(6) - OnF(7) -
Htr(8) - FHU(9) - ES(10) - Hdy(11)
d3d 0 Pr1 Digital input 3 activation delay 0 to 255 (min.)
nPS 15 Pr1
Number of pressure switch activation
before lock
0 to 15
OdC F-C Pr1
Compressor and fan status when open
door
no(0) - FAn(1) - CPr(2) - F-C(3)
rrd 30 Pr1 Outputs restart after door open alarm. 0 to 255 (min.)
CLOCK
CbP Y Pr1 Clock presence n(0) – Y(1)
Hur - - - Pr1 Current hour - - -
Min - - - Pr1 Current minutes - - -
dAY - - - Pr1 Current day Sun(0) - SAt(6)
Hd1 nu Pr1 First weekly day Sun(0) - SAt(6) - nu(7)
Hd2 nu Pr1 Second weekly day Sun(0) - SAt(6) - nu(7)
Hd3 nu Pr1 Third weekly day Sun(0) - SAt(6) - nu(7)
ILE 0.0 Pr1
Energy saving cycle start during
workdays
0 - 23.5(143)(hours.10min)
dLE 0.0 Pr1
Energy saving cycle length during
workdays
0 to 24.0(144)(hours.10min)
ISE 0.0 Pr1
Energy saving cycle start during
holidays
0 - 23.5(143)(hours.10min)
dSE 0.0 Pr1
Energy saving cycle length during
holidays
0 to 24.0(144)(hours.10min)
HES 0.0 Pr1
Temperature increasing during Energy
Saving cycle
[-54°F to 54°F]
[-30.0°C to 30.0°C]
Ld1 nu Pr1 Workdays First defrost start
0.0 to 23.5(143) - nu(144)
(hours.10min)
Ld2 nu Pr1 Workdays Second defrost start
Ld1 to 23.5(143) - nu(144)
(hours.10min)
Ld3 nu Pr1 Workdays Third defrost start
Ld2 to 23.5(143) - nu(144)
(hours.10min)
Ld4 nu Pr1 Workdays Fourth defrost start
Ld3 to 23.5(143) - nu(144)
(hours.10min)
Table 23-1 - Default Setting Values (Continued)