13
Note: dis=disable
Min
Default
ENGINE PLANT BATTERY ( )Engine->Plant battery
Max
BatteryUndervolts Shutdown
BatteryUndervoltsWarning
BatteryUndervoltsWarningReset
BatteryUndervoltsVoltsDelay
BatteryOvervolts Shutdown
BatteryOvervoltsWarning
11.0
BatteryOvervoltsWarningReset
6.0(dis)
6.0(dis)
30.0
30.0
11.5
6.0
1.0
0.0 120.0
29.0
28.5
Charge AlternatorWarning
dis
30.0
30.0
30.0
6.0 30.0
BatteryOvervoltsDelay
1.0
0.0
120.0
30.0
6.0(dis)
6.0(dis)
6.0(dis)
Under volt shutdown
Under volt warning
Under volt reset
Under volt delay
Over volt shutdown
Over volt warning
Over volt reset
Over volt delay
Alt. chg. warning
Unit
VZ
VZ
VZ
VZ
VZ
VZ
Sec
Sec
VZ
dis
dis
CANBUS ECU ( )Engine->CanBus ECU
Baud rate
J1939 ECU type
Device address
SPN version
Min
Default
UnitMax
0
7 4
31
0
0 255 17
1 3 1
kBaud
ECU remote control
Speed control enable
Oil pres cont. enab
Temp. control enable
ENABL
Device Address
0(dis)
SPNversion
ECURemoteControlviaJ1939
SpeedControlviaJ1939
OilPressureControlviaJ1939
Coolant TemperatureControlviaJ1939
Speed correction
50
SpeedCorrectionValue
%
0 100
Speed set point
1500
15001800/
SpeedSetPointSelection
RPM
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL/DISBL
ENABL
DISBL
DISBL
BaudRate:
0:20,1:50,2:100,3:125,
4:250,5:500,6:800,7:1.000
J1939ECU TypeSelection:
0-Disable
1-Standard
2-VolvoEMS1
3-VolvoEMS2
4-VolvoEMS2b
5-VolvoEDC3
6-VolvoEDC4
7-DeutzEMR2
8-DeutzEMR3
9-Perkins1300
10-Perkins ADEM3
11-Perkins ADEM4
12-ScaniaS6
13-MANMFR
14-CumminsISB
15-CumminsCM570
16-CumminsCM850
17-CumminsCM2150E
18-CumminsCM2250
19-DetroitDDEC
20-JohnDeere
21-MTU ADEC
22-MTUECU8
23-MTUECU8SAM
24- Yuchai
25-Kubota
26-BaudouinWISE10B
27-BaudouinWISE15
28-Perkins1600
29-Perkins A4E2
30-Perkins A5E2
31-Perkins A5E2v2