EasyManua.ls Logo

EMKO TRANS-AMF - Page 14

EMKO TRANS-AMF
29 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
Note: dis=disable
Min
Default
Unit
CANBUS ERROR SET ( )Engine->CanBus error set
Max
CanFault Actions:
0-Disable
1-WarningNon-Latching
2-Warning(AlarmOnly,NoShutdown)
3-Electrical Trip(Alarm/OffLoadGenerator
FollowedByShutdown AfterCooling)
4-Shutdown(Alarm AndShutdown)
0
0 2
0
0(dis) 4
CAN fault activation
CANfaultactions
SecCanFaultDelay
10
2 250
CAN fault delay
CanFault Activation:
0- ActiveFromStarting
1- ActiveFromSafetyOn
2- Always Active
J1939 AmberWarningLamp Actions:
0-Disable
1-WarningNon-Latching
2-Warning(AlarmOnly,NoShutdown)
3-Electrical Trip(Alarm/OffLoadGenerator
FollowedByShutdown AfterCooling)
4-Shutdown(Alarm AndShutdown)
2
0 2
0
0(dis) 4
Amber warn.activation
Amberwarn.actions
SecJ1939 AmberWarningLampDelay
2
0 250
Amber warn.delay
J1939 AmberWarningLamp Activation:
0- ActiveFromStarting
1- ActiveFromSafetyOn
2- Always Active
J1939RedStopLamp Actions:
0-Disable
1-WarningNon-Latching
2-Warning(AlarmOnly,NoShutdown)
3-Electrical Trip(Alarm/OffLoadGenerator
FollowedByShutdown AfterCooling)
4-Shutdown(Alarm AndShutdown)
2
0 2
0
0(dis) 4
Red stop activation
Redstopactions
SecJ1939RedStopLampDelay
2
0 250
Red stop delay
J1939RedStopLamp Activation:
0- ActiveFromStarting
1- ActiveFromSafetyOn
2- Always Active

Other manuals for EMKO TRANS-AMF