5
Note: dis=disable
600
60
60
60
600
600
600
VV
VV
VV
VV
60
Min
DefaultMAINS VOLT LEVEL ( )Mains->Volt level
Max
MainsUnderVoltage
MainsUnderVoltageReset
MainsOverVoltage
MainsOverVoltage Reset
320
340
440
420
Undervolttrip
4.1OperatorParameters
Undervoltreset
Overvolttrip
Overvoltreset
Unit
4.Parameters
Min
DefaultMAINS FREQ. LEVEL ( )Mains-> levelFrequency
Max
MainsUnderFrequency
Hz
Hz
Hz
Hz
20.0 75.0
20.0 75.0
20.0 75.0
20.0 75.0
45.0
48.0
55.0
52.0
MainsUnderFrequency Reset
MainsOverFrequency
MainsOverFrequency Reset
Underfreqtrip
Underfreqreset
Overfreqtrip
Overfreqreset
Unit
600
60(dis)
60
60
600
600
600
VV
VV
VV
VV
60(dis)
Min
Default
Max
GeneratorUnderVoltageShutdown
GeneratorUnderVoltagePre-Alarm
GeneratorUnderVoltagePre-AlarmReset
GeneratorOverVoltageShutdown
GeneratorOverVoltagePre-Alarm
320
340
350
440
60(dis) 600
60 600
420
400
GeneratorOverVoltagePre-AlarmReset
VV
VV
Undervoltshutdown
Undervoltprealarm
Undervoltreset
Overvoltshutdown
Overvoltprealarm
Overvoltreset
Unit
Shutdowndelaytime
GeneratorVoltageShutdownDelay Time
GENERATOR VOLT LEVEL ( )Generator-> levelVolt
0.0 10.0 1.0
Sec
75.0
30.0(dis)
75.0
75.0
Hz
30.0(dis)
Min
Default
Max
GeneratorUnderFrequencyPre-Alarm
GeneratorUnderFrequencyPre-AlarmReset
GeneratorOverFrequencyShutdown
GeneratorOverFrequencyPre-Alarm
GeneratorOverFrequencyPre-AlarmReset
45.0
46.0
58.0
55.0
54.0
GeneratorFrequencyShutdownDelay Time
Hz
Hz
Hz
Hz
30.0
30.0(dis)
30.0
75.0
75.0
Underfreqprealarm
Underfreqreset
Overfreqshutdown
Overfreqprealarm
Overfreqreset
Shutdowndelaytime
Unit
GENERATOR LEVEL ( )FREQ Generator-> levelFrequency
75.0
75.0
Hz
30.0
Nominal AlternatorFrequency
50.0
43.0
Hz
Nominalfrequency
Underfreqshutdown
GeneratorUnderFrequencyShutdown
30.0(dis)
0.0 10.0 1.0
Sec
4.1.1Mains
4.1.2 Generator
Min
Default
Max
GeneratorUnderCurrentPre-AlarmReset
GeneratorOverCurrentIDMT Alarm
GeneratorOverCurrentSet
GeneratorOverCurrentPre-Alarm
GeneratorOverCurrentPre-AlarmReset
Undercur. reset
Overcur.IDMTalarm
Overcur.set
Overcur.prealarm
Overcur. reset
Unit
GENERATOR ( )CUR LEVEL Generator->Current level
GeneratorUnderCurrentSet
Undercur.set
Undercur.prealarm
GeneratorUnderCurrentPre-Alarm
0 9999 9980
AV
0
0(dis)
0
0
0(dis)
9999
9999
9999
9999
9999
1
dis
5
DISBL
9999
9990
AV
AV
AV
AV
AV
ENABL/DISBL