EasyManua.ls Logo

Emotron VSA Series - Page 50

Emotron VSA Series
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Emotron AB 01-3991-11r2 Programming instructions and menu list 49
218
External control opera-
tion mode
000: Forward/ Stop-Reverse/Stop
001: Run/ Stop-Forward/Reverse
002: 3-wire-Run/ Stop
000
219
Remote keypad con-
trol selection
000: Disable (no signal loss detection)
001: Enable. On signal loss stop accord-
ing to [337]
002: Enable. Runs at the last set fre-
quency. On signal loss Stop is according to
[213] setting or Stop key on keypad.
000
Stop VSD
then
connect
remote
keypad
for
proper
opera-
tion *4
Main setup, Motor data
221 Rated motor voltage *4
222 Rated motor power *4
223 Rated motor current *4
224 Rated motor frequency *4
225 Rated motor speed 0 to 120 (x 100 RPM) *4
226 Carrier frequency 004 to 016 010 4–16K
Main setup, Motor protection
231 Run stall-prevention
000: Run stall prevention available
001: Run stall prevention unavailable
000
232
Run stall-prevention
level (%)
050 to 300 200
233
Stall prevention time
during run
000: According to dec. time set in [332]
001: According to dec. time set in [239]
000
234
Electronic thermal
relay protection for
motor (OL1)
000: Enable motor protection
001: Disable motor protection
000
235
Acceleration stall-pre-
vention
000: Acceleration stall prevention enable
001: Acceleration stall prevention disable
000
236
Acceleration stall-pre-
vention level (%)
050 to 300 200
237
Deceleration stall-pre-
vention
000: Deceleration stall prevention enable
001: Deceleration stall prevention disable
000
Ta bl e 2 3
Menu Function Description Range/ Code
Factory
Default
Remarks

Related product manuals