50 Programming instructions and menu list Emotron AB 01-3991-11r2
238
Deceleration stall-pre-
vention level (%)
050 to 300 200
239
Stall prevention decel-
eration time set
00.1 to 999 s 03.0
Main setup, Parameter set handling
241 Copy module
000: Copy module disable
001: Copy to module from VSD
002: Copy to VSD from module
003: Read/ write check
000 *3
242 Factory default
010: Reset to factory default (50 Hz)
020: Reset to factory default (60 Hz)
000
Main setup, Trip Autoreset
251 Auto-restart times 000 to 005 000
252
Auto Restart for power-
loss
000: Enable
001: Disable
001
Main setup, Serial communication
261
VSD communication
address
001 to 254 001 *3 *4
262 Baud rate (bps)
000: 4800
001: 9600
002: 9200
003: 38400
003 *3 *4
263 Stop bit
000: 1 Stop bit
001: 2 Stop bit
000 *3 *4
264 Parity bit
000: No parity
001: Even parity
002: Odd parity
000 *3 *4
265 Data bits
000: 8 bits data
001: 7 bits data
000 *3 *4
266
Communication time-
out detection
00.0 to 25.5 Sec 00.0 *3
Ta bl e 2 3