B
brucekempSep 23, 2025
What causes voltage too high during stop in Emotron VSC?
- FfdukeSep 23, 2025
If your Emotron Inverter shows 'Voltage too high during stop', it is caused by detection circuit malfunction. Send the VSD back to be repaired.
What causes voltage too high during stop in Emotron VSC?
If your Emotron Inverter shows 'Voltage too high during stop', it is caused by detection circuit malfunction. Send the VSD back to be repaired.
What to do if my Emotron Inverter displays a motor overload error?
If your Emotron Inverter displays a 'Motor overload' error, it could be due to a heavy load on the motor. In this case, you should increase the motor capacity. It may also be caused by inappropriate settings of parameters 0-02, 9-08 through 9-11. Ensure these parameters are properly configured.
What causes VSD overload in Emotron Inverter and how to fix it?
If your Emotron Inverter shows 'VSD overload,' it indicates that the load is too heavy for the VSD. To resolve this, increase the VSD capacity.
How to troubleshoot over-current at fixed speed on Emotron VSC?
If your Emotron Inverter shows 'Over-current at fixed speed', this could be due to a transient load or power change. To solve it, first, increase the capacity of the VSD. If that doesn't work, rerun parameter autotuning (0-06 = 1). As a last resort, reduce stator resistance (14-0) if the previous solutions don't help.
Why is my Emotron VSC Inverter overheating during stop and what can I do?
If your Emotron Inverter is overheating during stops, it could be due to a detection circuit malfunction or high ambient temperature with poor ventilation. For a detection circuit issue, the VSD should be sent back for repairs. If the ambient temperature is too high or ventilation is poor, improve the ventilation conditions.
What causes illegal CPU interruption in Emotron VSC Inverter?
If your Emotron Inverter shows 'Illegal CPU interruption', it is likely caused by outside noise interference. If this issue happens repeatedly, send the unit back to be repaired.
What does key operation error mean on Emotron VSC?
If your Emotron Inverter displays 'Key operation error', it could be due to pressing or while 1-06 is greater than 0 or running at a preset speed, or attempting to modify a parameter that cannot be modified during operation. The or key is only available for modifying the parameter when 1-06=0. Modify the parameter during STOP.
What does parameter setting error mean on my Emotron VSC Inverter?
If your Emotron Inverter displays 'Parameter setting error', it could be due to 3-01 being in the range of 3-13 ± 3-16 or 3-14 ± 3-16 or 3-15 ± 3-16, 3-00 equaling 3-01, or a setting error while performing Autotuning (e.g., 1-00=0, 1-06=0). Modify 3-13~3-15 or 3-16, ensure 3-00 is greater than 3-01, and set 1-00=0 and 1-06=0 during Auto tuning.
Why is the voltage too low during operation in my Emotron VSC Inverter?
If your Emotron Inverter shows 'Voltage too low during operation', it may be due to a power voltage that is too low or varies widely. To address this, improve the power quality or increase the value of parameter 2-01. Additionally, set a longer acceleration time, increase the VSD capacitor, or add a reactor at the power input side.
Why is the heatsink temperature too high during operation on my Emotron VSC?
If your Emotron Inverter displays 'Heatsink temperature too high during operation', it could be due to a heavy load or high ambient temperature with poor ventilation. First, check for any problems with the load. If the load is not the issue, increase the VSD capacity. Additionally, improve ventilation conditions to lower the heatsink temperature.