Emotron AB 01-3990-11r3 Software index 61
1- Start/Stop and Frequency Control Modes
Function
Code no.
Description Range/Code
Factory
setting
1-00
Run Command and
Source Selection
0000: Keypad
0001: External Run/Stop Control (see
1-01)
0002: Communication
0003: Built-in PLC
0000
1-01
Run/Stop-Forward/
Reverse Operation
Mode with External
Terminals
0000:Forward/Stop-Reverse/Stop
0001: Run/Stop-Forward/Reverse
0002: 3-Wire Control Mode-Run/Stop
0000
1-02
Prohibition of Reverse
operation
0000: Enable Reverse Command
0001: Disable Reverse Command
0000
1-03 Keypad Stop Button
0000: Stop Button Enabled
0001: Stop Button Disabled
0000
1-04
Starting Method
Selection
0000: Normal Start
0001: Enable Speed Search
0000
1-05
Stopping Method
Selection
0000: Controlled Deceleration-to-Stop
with DC Injection Braking (Rapid Stop)
0001: Free run Stop
1-06
Frequency Command
Source Selection
0000: Keypad
0001: Potentiomenter on Keypad
0002: External Analogue Signal Input
or Remote Potentiometer
0003: Up/Down Frequency Control
using MFIT (S1-S6)
0004: Communication Setting
Frequency
0005: Impulse (S5) setting frequency
(ver2.3)
000
1-07
Keypad Operation with
Up/Down Keys in Run
Mode
0000: “Enter” must be pressed after
frequency change with Up/Down Keys
on keypad.
0001: Frequency will be changed
directly when Up/Down Keys are
pressed.
0000