62 Software index Emotron AB 01-3990-11r3
2- Manual/Automatic Restart Modes
Function
Code no.
Description Range/Code
Factory
setting
Re-
marks
2-00
Momentary Power
Loss and Restart
0000: Momentary power loss
and restart disable
0001: Momentary power loss
and restart enable
0002: Momentary power loss
and restart enable while CPU is
operating. (According to the
capacity of DC power)
0000
2-01
Momentary Power
Loss Ride-Thru Time
(Seconds)
0.0 to 2.0 0.5
2-02
Auto Restart Delay
Time (Seconds)
0.0 to 800.0 0.0
2-03
Number of Auto
Restart Attempts
0 to 10 0
2-04
Auto Restart
Method
0000: Enable Speed Search
0001: Normal Start
0000
2-05
Direct Running After
Power Up
0000: Enable Direct running
after power up
0001: Disable Direct running
after power up
0001 *8
2-06 Delay-ON Timer (s) 0.0 to 300.0 0.0
2-07 Reset Mode Setting
0000: Enable Reset only when
Run command is Off
0001: Enable Reset when Run
command is On or Off
0000
2-08
Kinetic Energy
Back-up
Deceleration Time
0.0: Disable
0.1 to 25.0: KEB Deceleration
Time
0.0