Emotron AB 01-3990-11r3 Software index 63
3- Operating Parameters
Function
Code no.
Description Range/Code
Factory
setting
Re-
marks
3-00 Frequency Upper Limit (Hz) 0.01 to 650.00
50.00/
60.00
*4
3-01 Frequency Lower Limit (Hz) 0.00 to 650.00 0.00 *1
3-02 Acceleration Time #1 (s) 0.1 to 3600.0 10.0 *1
3-03 Deceleration Time #1 (s) 0.1 to 3600.0 10.0 *1
3-04 S-Curve Acc/Dec #1 (s) 0.0 to 4.0 0.2 *1
3-05 S-Curve Acc/Dec #2 (s) 0.0 to 4.0 0.2 *1
3-06
Acceleration Time #2 (MFIT)
(s)
0.1 to 3600.0 10.0 *1
3-07
Deceleration Time #2
(MFIT) (s)
0.1 to 3600.0 10.0 *1
3-08
Jog Acceleration Time
(MFIT) (s)
0.1 to 25.5 0.5 *1
3-09
Jog Deceleration Time
(MFIT) (s)
0.1 to 25.5 0.5 *1
3-10
DC Injection Brake Start
Frequency (Hz)
0.1 to 10.0 1.5 *1
3-11 DC Injection Brake Level (%) 0.0 to 20.0 5.0 *7
3-12 DC Injection Brake Time (s) 0.0 to 25.5 0.5 *1
3-13 Skip Frequency #1 (Hz) 0.00 to 650.00 0.0 *1
3-14 Skip Frequency #2 (Hz) 0.00 to 650.00 0.0 *1
3-15 Skip Frequency #3 (Hz) 0.00 to 650.00 0.0 *1
3-16
Skip Frequency Bandwidth
(±Hz)
0.00 to 30.00 0.0 *1
3-17 Parameter Lock
0000: Enable all Func-
tions
0001: 6-00 to 6-08 can-
not be changed
0002: All Functions
Except 6-00 to 6-08 can-
not be changed
0003: Disable All Func-
tion
0000