EasyManuals Logo

ENDA ETC1311 User Manual

ENDA ETC1311
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Technical Specifications
ThankyouforchoosingENDA ETC1311temperaturecontroller.
Readthisdocumentcarefullybeforeusingthisdevice. Theguaranteewillbeexpiredby
damagingofthedeviceifyoudon'tattendtothedirectionsintheusermanual. Alsowedon't
acceptanycompensationsforpersonalinjury,materialdamageorcapitaldisadvantages.
* 35 x 77mm sized.
* On-Off control.
* Having CE mark according to European Norms.
* TC Typ “J” or “K” or Pt100 input.
* Temperature compensation.
* In the case of probe failure, heating can be
selected on, off or periodical running.
* Upper and lower limits of the setpoint can be
adjusted.
* Set value can be adjusted by using single key.
Attention!
ENDA ETC1311isintendedforinstallationincontrolpanels.Makesurethatthedeviceis
usedonlyforintendedpurpose. Theelectricalconnectionsmustbecarriedonbya
qualifiedstaffandmustbeaccordingtotherelevantlocallyapplicableregulations.During
aninstallation,allofthecablesthatareconnectedtothedevicemustbefreeofenergy.
Thedevicemustbeprotectedagainstinadmissiblehumidity,vibrations,severesoiling
andmakesurethattheoperationtemperatureisnotexceeded. Thecablesshouldnotbe
closetothepowercablesorcomponents.
Panel cut-out
Dimensions
Note:
1)Panelthickness
shouldbemaximum
7mm.
2)Ifthereisno60mm
freespaceattheback
sideofthedevice,it
wouldbedifficultto
removeitfromthe
Panel
Holding screw 0.4-0.5Nm
Equipment is protected throughout
by DOUBLE INSULATION.
71mm
29mm
Flush mounting
clamp
Flush mounting
clamp
Forremovingmountingclamps:
Pushouttheflush-mounting
clampindirection asshown
inthefigurebelow. Then,pull
outtheclampindirection
1
2.
ENDA ETC1311 DIGITAL THERMOSTAT
ENVIRONMENTAL CONDITIONS
Height
Max. 2000m
80 , up to 40% 31°C decreasing linearly 50% at °C
Ambient/storage temperature
Max. relative humidity
0 ... +50°C/-25 ... 70°C (with no icing)
Rated pollution degree
According to EN 60529 Front panel : IP65
Rear panel : IP20
Do not use the device in locations subject to corrosive and flammable gasses.
Supply voltage /
230VAC +10%/-20%, 50/60Hz, 24VAC±10%,50/60Hz or 24Vac/dc (9-30Vdc or 7-24Vac)
Power consumption
Max. 4VA
2.5mm² screw-terminal connections.
3 digits, 14mm, 7 parts red LED
Wiring
Scale
Sensitivity/Accuracy
Indicator
EMC
Safety requirements
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
The device is designed to operate in controlled electromagnetic environment)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
ELECTRICAL CHARACTERISTICS
TE Typ “J” or “K”: / Pt100: -100...600°C0 ... +600°C
± ±
0.5% (of full scale) 1 digit/
OUTPUT
HEAT OUT
For Relay: 250V AC, 8A( ), NO+NC.ETC1311-XX ; for resistive load
For ETC1311-XXP ; Relay: 250V AC, 16A(for resistive load), NO.
For ETC1311-XX ;
For ETC1311-XXP ; Mechanical 30.000.000; Electrical 30.000 operation.
Mechanical 30.000.000; Electrical 100.000 operation.
Life expectancy for relay
CONTROL
Control type Single-setpoint control
On-Off control
Control algorithm
Hysteresis
Adjustable between 1 ... 20°C.
HOUSING
Housing type
Suitable for flush-panel mounting.
Dimensions
W77xH35xD71mm
Weight
Approx. 250g ( )after packing the device and a probe
Enclosure material
Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
4
5
SUPPLY:
NOTE:
184-253V AC
50/60Hz 3VA
Line
Neutral
230V AC
Supply
Switch
Note:
Cable size: 1,5mm²
Fuse
F 100 mA
250V AC
Fuse should
be connected
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
SURAN
Industrieelektronik
DettingerStr.9
D-72160Horba.N.
Tel.:+49(0)7451/625617E-mail:info@suran-elektronik.de
Fax:+49(0)7451/6250650Internet:www.suran-elektronik.de
uptodate:01022014,modificationreservedandcanbechangeanytimepreviousnotice!
english
SN: XXXXXXXXX
1 2 3 4 5 6
7 8 9
10
11 12
ETC1311-K-230VAC
DIGITAL THERMOSTAT
K (NiCr-Ni)
-
+
ENDA INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 4VA
HEAT OUT
250V AC 8A
RESISTIVE LOAD
SN: XXXXXXXXX
1 2 3 4 5 6
7 8 9
10
11 12
ETC1311-FE-230VAC-P
DIGITAL THERMOSTAT
J (Fe-CuNi)
-
+
ENDA INDUSTRIAL ELECTRONICS
230V AC +10% -20%
50/60Hz 4VA
HEAT OUT
240V AC 16A
RESISTIVE LOAD
SN: XXXXXXXXX
1 2 3 4 5 6
7 8 9
10
11 12
ETC1311-RT-12VAC
DIGITAL THERMOSTAT
Pt100
ENDA INDUSTRIAL ELECTRONICS
12V AC 10%
50/60Hz 4VA
±
HEAT OUT
250V AC 8A
RESISTIVE LOAD
1./2ETC1311-E
SET
PRG
ETC1311
ENDA
OUT
°C
Order Code : ETC1311---
1 - Input
FE.....Fe-Const(J)
RT.....Pt100
K.......NiCr-Ni(K)
2 - Supply Voltage
230VAC...230V AC
24VAC.....24V AC
12VAC.....12V AC
SM...........9-30VDC/7-24V AC
3 - Output
P.........Relay-16A
None...Relay-8A
SSR....Logicoutput
1 2 3
SET
PRG
ETC1311
ENDA
OUT
°C
SN: XXXXXXXXX
ETC13 -K-230VAC
DIGITAL THERMOSTAT
11
ENDA INDUSTRIAL ELECTRONICS
HEAT OUT
250V AC 8A
RESISTIVE LOAD
1 2 3 4 5 6
7 8 9
10
11 12
230V AC +10% -20%
50/60Hz 4VA
K (NiCr-Ni)
-
+
1
35mm
77mm
Depth
Panel
2
71mm
5mm
Rubber
packing

Other manuals for ENDA ETC1311

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ENDA ETC1311 and is the answer not in the manual?

ENDA ETC1311 Specifications

General IconGeneral
BrandENDA
ModelETC1311
CategoryThermostat
LanguageEnglish

Related product manuals