EasyManua.ls Logo

Endress+Hauser iTHERM TM411 - Page 16

Endress+Hauser iTHERM TM411
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
iTHERM TM412
16 Endress+Hauser
U
1
2
3
4
A0008946
 3 Installation examples
1, 2 Perpendicular to flow direction, installed at a minimum angle of 3° to ensure self-draining
3 On elbows
4 Inclined installation in pipes with a small nominal diameter
U Immersion length
In the case of pipes with a small nominal diameter, it is advisable for the tip of the thermometer
to project well into the process so that it extends past the pipe axis. Installation at an angle (4)
could be another solution. When determining the immersion length or installation depth all the
parameters of the thermometer and of the medium to be measured must be taken into account
(e.g. flow velocity, process pressure).
The use of iTHERM QuickSens inserts is recommended for immersion lengths U <
70 mm (2.75 in).
1 2
A0008947
 4 Process connections for thermometer installation in pipes with small nominal diameters
1
Varivent
®
process connection type N for DN40
2 Tee or elbow thermowell (illustrated) for weld-in as per DIN 11865 / ASME BPE

Related product manuals