Tx62, TTSP-RT0111, TTSP-CT1121 XA01137T
Endress+Hauser 7
Safety
instructions:
General
Hazardous area
Zone 1, 2
Hazardous area
Zone 1, 2
Non-hazardous
area
Ta
#
Local potential equalization
Protection by
thermowell
#
Ta 100 °C with terminal block≤
Supply of sensor:
U 5 V DC
I 10 mA
≤
≤
Tp
A0023378-EN
• Comply with the installation and safety instructions in the operating
instructions.
• Install the device according to the manufacturer's instructions and
any other valid standards and regulations (e.g. IEC 60079-14).
• Seal the cable entries tight with certified cable glands for type of
protection Ex e and an appropriate temperature range of the ultimate
application.
• Seal the cable entries tight with certified cable glands (min. IP54)
IP6X according to IEC 60529.
• During operation, the cover must be screwed all the way in and the
cover's safety catch must be fastened.
• The housing of the thermometer must be connected to the local
potential equalization.