Wiring
17
4.2.6 Additional information on Modbus EIA485
Connection
As described in the “Modbus over serial line specification and implementation guide V1.02”
published by the Modbus-IDA organisation (www.modbus.org) and based upon the EIA/TIA-485-
A physical layer specification, Modbus two-wire serial requires the following four electrical
connections between each of the devices on the bus.:
Additional bus settings
Bus biasing resistors (must be present at one point on the bus) (always enabled inside NXA820)
Bus termination resistor (must be present at each end of the bus) (software selectable inside
NXA820)
Cable Specification
Terminal Signal Purpose Remarks
10 A Data signal (-) These signals must be connected using a balanced twisted pair cable.
11 B Data signal (+)
12 C Signal Common Must interconnect all devices on the bus.
13 Shield EMC Protection Copper braided or combined foil and braided shielding.
Characteristic impedance 135 to 165 Ω at measuring frequency of 3 to 20 MHz
Cable capacitance 30 pF/m
Core cross-section 0.34 mm
2
, corresponds to AWG 22, multi-strand cable is preferred
Cable type Single twisted pair + third conductor (for common)
or
Dual twisted pair (common uses second pair with wire joined together)
Cable resistance 110 Ω/km
Signal damping Max. 9 dB over the entire length of the cable cross-section
Shielding Copper braided shielding or combined foil and braided shielding