EasyManua.ls Logo

Endress+Hauser Tankvision NXA820 - Terminal Assignment for Host Link NXA822

Endress+Hauser Tankvision NXA820
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wiring
21
4.4 Terminal assignment for Host Link NXA822
L00-NXA82xxx-04-00-00-yy-021
A: Power supply; B: Fuse; C: Status relay; D: System LAN port; E: Sync Link LAN port; F: Service LAN port;
G: RS232 Host connection; H: RS485 Host connection; I: Endress+Hauser CDI port; J: Display port; K: USB port;
L: Weights & Measures locking switch
4.4.1 Power supply
Connector: Phoenix 7.62 GMSTB/GFKC
4.4.2 Status Relay
Connector: Phoenix FKC 2,5HC/3-St-5,08
!
Note!
The depicted switching state of the relay refers to the de-energized state.
23
1
6
7
8
W&M
RESET
RESET
NXA Status
Relay
E
L+
L-
6
7
8
3
2
1
Fuse
POWER
10,5 ... 32V DC
2AT
DTR
DSR CTS
RTS
RS485
RS232
C
B
A
18
17
16
A
B
C
D E
F
G
H
I
J
K
L
Terminal Meaning for AC version
(90-250 VAC)
NXA822 - **1******
Meaning for DC version
(10.5-32 VDC)
NXA822 - **2******
(in preparation)
1L L+
2N L-
3 Potential equalization Potential equalization
Fuse 400 mA T Fuse 2 A T
Terminal Meaning Remarks
6 normally open contact
NXA operating normally:
terminals 7 & 8 are interconnected
NXA powered off or fault status condition:
terminals 6 & 8 are interconnected
7 normally closed contact
8 switching contact

Other manuals for Endress+Hauser Tankvision NXA820