© COPYRIGHT 2016 ENTERGIZE, LLC. ALL RIGHTS RESERVED. P/N 71969 3220-2345 REV 00=E
1
SET CLOCK, YEAR, MONTH, DAY
1. Press ▲/ ▼ to select 12 / 24 Hr mode, then press Next.
2. Press ▲/ ▼to select hour, then press Next.
3. Press ▲/▼to select minutes, then press Next.
4. Press ▲/ ▼ to select current year, then press Next.
5. Press ▲/ ▼ to select current month, press Next.
6. Press ▲/ ▼ to select the calendar day number.
7. Press Done to complete operation.
note: Select More > Clock, to access after setup.
ACCESS SERVICE MENUS
1. Hold lower right and left keys for fi ve seconds.
2. Press Next or Go Back to select a Service Menu.
3. Press ▲/ ▼ to select option.
4. Press Done when complete.
CONFIGURE SERVICE MENUS
The following Service Menus (SM) commonly require
confi guration. Please verify that these are set for your
specifi c application. additional confi guration may be
required. refer to Table 2 for all available Service Menus.
SM 100 = Programmable or nonprogrammable
SM 110 = System Type
SM 121 = number of fan Speeds
SM 130 = reversing valve
SM 135 = W1 heat output no or nc
SM 170 = remote Sensors
SM 265 = Single or dual Setpoint operation
WIRE TERMINAL DESIGNATIONS
1. connect wires for appropriate system type (Table 1).
WARNING: DISCONNECT POWER BEFORE BEGINNING INSTALLATION.
CAUTION: Use copper wire only. Insulate or wire-nut all unused leads.
Use care to avoid electrostatic discharge to thermostat
CAUTION: Do not connect unused wires together
ALL ELECTRICAL LOADS MUST BE CONNECTED TO TERMINAL C
(24 VAC).
TABLE 1. TERMINAL BLOCK
Fan Coil (Conventional) Heat Pump
C 24 VAC, Unswitched side C 24 VAC, Unswitched side
W1 Stage 1 Heat B/O Reversing Valve
W2 Stage 2 Heat AUX Auxiliary Heat (Stage 2 or 3)
G FAN High G FAN High
A FAN Medium A FAN Medium
E FAN Low E FAN Low
Y1 Stage 1 Cool Y1 Compressor Stage 1
Y2 Stage 2 Cool Y2 Compressor Stage 2
RH
24 VAC Power for heating,
switched side
RH
24 VAC Power for heating,
switched side
RC
24 VAC Power for cooling,
switched side
RC
24 VAC Power for cooling,
switched side
SC Sensor Common SC Sensor Common
S1 Indoor Remote Sensor S1 Indoor Remote Sensor
S2 Occupancy Sensor S2 Occupancy Sensor
S3
Seasonal Changeover Switch
OPEN=Cooling in Summer
CLOSED=Heating in Winter
S3 NA
!
24 VAC Switched Side
OPEN= Summer CLOSED = Winter
C
WI
Y1
G
A
E
RH
RC
SC
S1
S2
S3
OCC Sensor
Aquastat
FAN LO
FAN MED
FAN HIGH
Cool Valve
Heat Valve
Sensor Common
Remote Sensor
24 VAC Unswitched
24 VAC
TYPICAL FAN COIL
WIRING DIAGRAM
5
41
3
2
QUICK START GUIDE
PERFORMANCE PRO MULTI-
FAN
OCCUPANCY THERMOSTAT
NOTE:
Display of
Clock is not
available when
for non-
programmable
operation.
Service
Menu
Current
option
FAN HIGH
FAN MED
FAN LOW
1. Press the Fan button to
select speed/operation.
2. Press
Done when complete.
fan Speed is noted as
follows:
on = continuous fan operation
AUTO = Fan Cycles with Heating
and Cooling
FAN SPEED
SELECTION
6
Question and Answer IconNeed help?

Do you have a question about the Entergize T8532OCC and is the answer not in the manual?

Entergize T8532OCC Specifications

General IconGeneral
BrandEntergize
ModelT8532OCC
CategoryThermostat
LanguageEnglish

Summary

Set Clock, Year, Month, Day

Configure Service Menus

Wire Terminal Designations

Setback Operation Notes

Occupied Timer

Sets time before control goes to setback after last detection. Controls ramping process.

Setback Values

Sets HEAT and COOL set points for setback. Values can be set to OFF or 50-90F.

Night Lock ON Protection

Holds user set point between 10 PM and 8 AM when occupancy is detected.

Advanced Configuration

System Type

Select appropriate system configuration for available service menus.

Fan Speeds

Allows selection of multiple fan speeds (1, 2, 3, or 4).

O/B Reversing valve

Configure reversing valve output for cooling or heating.

Service Menu Details

Setback Low

Set thermostat heat setpoint for setback mode.

Setback High

Set thermostat cool setpoint for setback mode.

Occupied Sensor Operation

Enable or disable occupancy sensor operation.

Occupied Timer Duration

Sets time required to go into setback after last detection.

Setback Ramping

Determines how fast the control will setback (Economy, Comfort 1, Comfort 2).

Nighttime Lock On

Locks thermostat to Occupied mode after 10:00pm, resets at 08:00am.

Additional Service Menu Details

Factory Default Reset

Enable or disable returning the device to factory default settings.