Page #10 background image
JOHNSON CONTROLS
10
FORM ET115.24-NOM5 (908)
COOLING/HEATING MEDIUM CONNECTIONS
Toxic residues and loose particles resulting from manufacturing and eld piping techniques
such as joint compounds, soldering ux, and metal shavings may be present in the unit and
the piping system. Special consideration must be given to system cleanliness when connecting
to solar, domestic or potable water systems.
AIRFLOW POWER
CFM QT QS Flow Rate WPD INPUT
(DRY FLOW) (BTUH) (BTUH) GPM ft-wg (WATTS)
HLF 20 3 10 330 7800 6100 1.8 1.6 81
HLF 25 3 10 450 11500 8500 2.6 3.4 138
HLF 30 3 10 640 13900 11000 3.2 7.6 152
HLF 40 3 10 800 18500 14300 4.2 3.7 263
HLF 50 3 10 1140 24000 19300 5.4 7.4 402
HLF 60 3 10 1590 34000 26500 7.6 14.6 489
HLF 20 4 10 320 8500 6000 1.8 3.1 77
HLF 25 4 10 430 11600 8600 2.6 6.6 135
HLF 30 4 10 610 16900 12600 3.9 10.9 151
HLF 40 4 10 780 21900 16400 4.9 7.2 261
HLF 50 4 10 1040 28500 225
00 6.4 12.9 380
HLF 60 4 10 1510 41400 31300 9.2 27.1 466
HLP 20 3 10 270 6900 5300 1.6 1.2 81
HLP 25 3 10 420 10900 8100 2.5 3.1 132
HLP 30 3 10 540 12600 9800 2.8 6.1 152
HLP 40 3 10 770 18100 13900 4.1 3.5 263
HLP 50 3 10 1010 22300 18200 5.0 7.1 372
HLP 60 3 10 1460 32300 25600 7.2 13.3 489
HLP 20 4 10 260 7400 5200 1.6 2.5 77
HLP 25 4 10 410 10900 8100 2.5 6.0 130
HLP 30 4 10 520 15600 11500 3.5 10.0 151
HLP 40 4 10 740 21300 15900 4.8 6.9 261
HLP 50 4 10 970 27200 21400 6.1 11.9 361
HLP 60 4 10 1370 38600
29700 8.6 23.8 466
HLE 20 3 10 240 6300 4800 1.5 1.1 75
HLE 25 3 10 310 8900 6500 2.0 2.2 127
HLE 30 3 10 450 11100 8600 2.5 4.9 135
HLE 40 3 10 650 16300 12400 3.7 2.9 245
HLE 50 3 10 820 19500 15700 4.4 5.6 337
HLE 60 3 10 1130 27500 21500 6.1 10.0 402
HLE 20 4 10 240 6300 4700 1.5 2.1 65
HLE 25 4 10 300 8700 6300 2.0 4.0 125
HLE 30 4 10 440 13600 10000 3.1 7.9 130
HLE 40 4 10 630 18900 14000 4.2 5.5 235
HLE 50 4 10 780 23400 18300 5.3 9.1 321
HLE 60 4 10 1040 31900 24200 7.1 16.8 383
COIL COOLING CAPACITY
WATER
MODEL /
SIZE Rows FPI
NOTE: Based on 80°F DB
and 67°F WB EAT, 45°F
EWT, 10°F temperature
rise, high fan speed.
Motor type is PSC and
motor voltage is 115/1/60.
Airflow under dry coil con-
ditions. Model HLE tested
at 0.0" external static pres-
sure. Models HLF and HLP
tested at 0.05" external
static pressure.
ARI STANDARD RATINGS
LD13887