11 energiSava
®
325
SHOULD YOU ENCOUNTER ANY PROBLEMS INSTALLING
THIS UNIT, CALL US ON: 0345 27 27 810
Commissioning
Controls
The fan speeds of the energiSava
®
325 will require adjustment to ensure the flow rates
achieved provide adequate ventilation. The energiSava
®
325 has 2 standard fan speed settings
continuous speed and boost speed.
The continuous speed and boost speed are programmed by placing the controller into program
mode via the program/run switch and changing the position of the rotary potentiometers.
When applying power for the first time, the unit can take up to four minutes to start operating.
Prior to the first commission set continuous speed potentiometers to minimum and boost
speed potentiometers to maximum or reset the controller.
Program
Switch
Humidity
Timer
Potentiometers
Extract Supply
Run
Humidity
Sensor
Extract
Supply
Boost
Continuous
Boost
Overrun
Timer