PIV & MIV Air Source / Inline
01423 859 395
SHOULD YOU ENCOUNTER ANY PROBLEMS
INSTALLING THIS UNIT, CALL US ON:
15
Fire Safety
Smoke Kits
For installations with a floor more than 4.5m above ground, a
compatible smoke kit must be fitted. The kits listed below contain
all the extra parts and instructions required:
Order Code Description
KIT-PIV-SMOKE-125 PIV smoke kit with 1x 125mm diffuser
KIT-PIV-SMOKE-150 PIV smoke kit with 1x 150mm diffuser
KIT-PIV-SMOKE-200 PIV smoke kit with 1x 200mm diffuser
KIT-MIV-SMOKE-125 MIV smoke kit with 2x 125mm diffusers
Smoke Alarms
For installations with a floor more than 4.5m above ground, the unit
must be wired into a smoke alarm in order to switch the unit off upon
the detection of smoke.
The unit can be wired into an existing smoke alarm (check compatibility
with the smoke alarm manufacturer). All wiring should be completed
by a competent person.