22
US-Unit
Analogue output [0...10 V / 0(4)...20 mA] from to unit
low (L1) high (H1)
standardized DN15: 0 35 70 SCFM
volumetric flow DN20: 0 60 120 SCFM
DN25: 0 100 200 SCFM
DN32: 0 165 330 SCFM
DN40: 0 260 520 SCFM
DN50: 0 410 820 SCFM
mass flow DN15: 0 75 150 kg/h
DN20: 0 140 280 kg/h
DN25: 0 220 440 kg/h
DN32 0 360 720 kg/h
DN40: 0 570 1140 kg/h
DN50: 0 890 1780 kg/h
standardized flow
≤DN50 0 20000 40000 SFPM
Temperatur alle Ø -4 176 176 °F
Switching output [switching point/hysteresis]
standardized DN15 30/3 60/6 SCFM
volumetric flow DN20 50/5 100/10 SCFM
DN25: 80/8 160/16 SCFM
DN32: 130/13 260/26 SCFM
DN40: 210/21 420/42 SCFM
DN50: 330/33 660/66 SCFM
mass flow DN15: 60/6 120/12 kg/h
DN20: 110/11 220/22 kg/h
DN25: 200/20 400/40 kg/h
DN32: 290/29 580/58 kg/h
DN40: 460/46 920/92 kg/h
DN50: 700/70 1400/140 kg/h
standardized flow
≤DN50 15000/1500 30000/3000 SFPM
temperature
all Ø 90/9 150/15 °F
Pulse output pulse-value = 1CF pulse-duration = 0.1 sec.
CONFIGURATION SOFTWARE
LIMITED LIABILITY
E+E Elektronik shall not be held liable for any damages or consequential damages (for example, but not
restricted to, loss of earnings, interruption of business, loss of information and data or any other financial
losses) resulting from the installation, use or impossibility of use of an E+E Elektronik software product and
any associated support services or non-performance of support services.
1. General
The configuration software can be downloaded free of charge at www.epluse.com/ee771
The configuration software, allows for a user-friendly adaptation of the flow meter to the application. In addi-
tion, the measurement values for flow and temperature can be calibrated / adjusted.
The system requirements for the installation and execution of the software are:
• Windows XP with SP3, Windows Vista or Windows 7
• .NET framework 3.5 with SP1
• USB 2.0 interface
During setup there will be no installation of .NET Framework 3.5 SP1 – if the required version is not already
installed on the computer the following error message will appear at the start of the configuration software.
.NET Framework 3.5 SP1 can be installed using Windows Update.