3 Technical Data Page 6
3. Technical Data
Oil-Fired Warm Air Heaters
Model
P 40
P 60
P 80
P 100
P 120
Output kcal/h
kW
BTU
34000
40
136500
51000
60
204700
69000
80
273000
86000
100
341200
103000
120
409450
Fuel consumption l/h
Kg/h
4
3,1
6
4,7
8
6,2
10
7,8
12
9,4
Air output m
3
/h
cfm.
4400
2596
6200
3658
7700
4543
7700
4543
7700
4543
Motor speed 50Hz rpm
Motor speed 60Hz rpm
1400
1400
1400
1400
1370
1650
Electric Tension 50-60Hz V
230
230
230
230
230
Electric current 230V-50Hz A
230V-60Hz A
2,2
2,5
3,5
3,5
4,5
4,6
Power 230V-50Hz W
230V-60Hz W
480
550
770
770
1035
1058
Sound pressure dBA
67
70
73
73
76
Weight Kg
48
51
55
55
65
Throw ventilator m
30
30
40
40
50
Length mm
1288
1288
1288
1288
1488
Height mm
455
515
570
570
570
Width mm
521
576
624
624
624
Distance centre brackets* mm mm
800
800
800
800
800
*Option, when mounted
The P 40 - P 120 consists of 4 main components:
1. Shell : used for air supply.
2. Combustion chamber : the oil/air mixture is burned in the chamber and ignited by spark ignition.
3. Ventilator : this conveys the hot air into the room, supplies the air needed for
combustion and the air for cooling the combustion chamber and the flue
gases.
4. BCU : the Burner Control Unit; the regulation and safety apparatus.
Description of materials:
Shell and burner chamber : High-grade 430 stainless steel
BCU : PPE (Environment temperature BCU: -10ºC to +60ºC)
The materials used are capable of withstanding the maximum loads.