EasyManua.ls Logo

EST LSS4 - Modules

Default Icon
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System
Installation
System
Modules
Standby
Current
Master
panelw/4
zones
ClassA
card
4-Wire
Smoke
Power
LSS4
Master
Panel
Assembly
(120
vAC/23o
VAc)
Table
2-3:
LSS4
Master
Panel
Specifications
Initial ng
Device
Circuits
(IDC)
Voltage
Supervisory
Currentper
circuit
I4aximum
Short
circuit
current
EOL
Resistor
European
mode
(StyleC)
Short
Circuit
Resistance
Notification
Appliance
Circuit
(NOTE2)
Voltage
Maximum
Currentper
circuit
(NOTE1)
EOL
Resistor
Auxiliary
Power
Voltage
Maximum
Current
(NOTE1)
General
Panel
Open
Collector
outputs,per
circuit
Input
Voltage
(120VAC
Model)
lnput
Voltage
(220VAC
Model)
Temperature
Humidity
Battery
charger
Maximum
charging
current
Alarm
Silence/Reset
Inhibit
Timer
Alarm
SignalCutoff
Timer
Maximum
supervisorycu
rrent
available
Maximum
wire
sizeany
terminal
Alarm
Contacts
Type
Rating
2.10
100mA
10mA
20
- 27 VDC See
Note#1
16.1to
26.48VDC
6 mA
70mA
3.9KU
100U
19.7
-
26.7VDC
3?A
15KU
20-27VOC
1.5A
30
VDC,100mA.
,current
sink
120
VAC,2A,60Hz
230
VAC,
1.5A,50 Hz
-
49°C
(32°
-
120°F)
85%
Non-Condensing
30AH
Max.@ 24VDC
1.52A
0 to99
Minutesin1
Min.
Increments
0 to99
Minutesin1
Min.
Increments
1.0A
12AWG
SPDT
120
VAC/30
VDC,2A
max.,
inductive.35pF
t4ole
4:
Maximum
current
from
all
circuits
directly
poweredbythe
LSS4
Master
Panelcannot
exceed4.5amps.
Refertothe
battery
calculation
sheetfor
detailed
information.
Note2:NAC #1andNAC U are
temporally
silenced
during
RMOD
solenoid
release
in
pulse
mode
only.
LSS4
Installation,
Operation,and
Maintenance