8ZEXP
Eight
Zone
Expansion
Module
System
lnstaliation
Table
2-10:
8ZEXP
Eight
Zone
Expansion
Card,
Rev.B
Specifications“
Standby
Current
Alarm
Current
1 16mA
116mA+ 11 mA/
Alarmed
Zone
Initiating
Device
Circuits
Voltage 161 to
26.48VDC
Supervisory
Current/
zone 9 mA
Maximum
Short
circuit
current 18 mA
EOL
Resistor
3.9 <O
Module
space
required two
Open
Collector
outputsper
zone 30
VDC,100
mA.,
current
sink
European
Mode
(StyleC)
Short
Circuit
Resistance 100U
"All
Revision“B”
8ZEXP
Cards
workin
European
Mode.
Installation
Referto
Figure
2-2.or
Fieure
2-3,or
Fieure2 4.
Note:The
8ZEXP,
RevisionB
mustbe
usedfor
LSS4'52
panel
appl
ications.
1.
Removethe
expansion
module
front
cover
plateand
mounting
frame
fromthe
enclosure(6,
10.4).
2.
Set the
addressesofthe
8ZEXP
module
(Table2-11
).The
8ZEXP
module
requires
tw'o(2)
addresses.Use the
jumperstosettheI
o+'esi
ofthetwo
addresses
assignedtothe
module.
lnstalI the m
oduleonthe
nylon
standoffson
frontoftheex
pansion
frame(1
6).
4.
Installany
4CLA
ClassA or
4REXP
option
modules
(7,9).
Connectthe
power/'data
cable
(P.'N250
150)
tromP7ofthe
LSS4
master
panel
assemblytoPSofthe
8ZEXP
module.
6.
Re-installthe
expansion
frameinthe
enclosure
(16,4).
7.
Installthe
frontco er
plateon the
expansion
frame
(10,6).
8.
Reconfigure
panel.
Referto
Chapter3.
I_SS4
Installation,
Operation,and
Maintenance
Manual
2.23