Panel
Configuration
Reviewingthe
Panel's
Configuration
3.14
1
Press
the
TROUBLE
SILENCE
[incrementto
previous
menu]
switch
untilthe
main
(level0)
menu
is
reached.The
NORMAL
LEDON
anda0inthe
display
indicatethe
panel
is in the
”select
system
parameter”
configuration
mode.
2
Pressthe
DRILL/TEST
[review]
switch.The
display
will
flashthe
configured
system
parameter
numbersas
listed
below.
Parameters2
and3 are
followedbythe
"tens"and "units"
digitsof the
timer
settings.Use the
RESET
[increment]
switchto
step
throughthe
system
variables.
Parameters
thatare not
displayedarenot
active.
O =
Alarm
silence/reset
inhibitand
alarm
signal
cutoff
timers
disabled;
CanadianandEuropean
Pre-Alarm
timers
disabled.
I =
Alarm
silence/reset
inhibit
timer
2 =
Alarm
signal
cutoff
timer
3 =
AC/brownout
delay
timer
enabled.
4 =
European
Mode
Selected.
5 =
Canadian
mode
selected
withpre
-alarm
timer
value
displayed.
3
Pressthe
TROUBLE
SILENCE
[incrementto
previous
menu]
switch
to
returntothe
main
(level0)
menu
4
Pressthe
RESET
(increment]
switchto
returnto
steptothe
"configureIDC
input
zone"
menu,as
indicatedby the
ALARMLED
ONanda1inthe
display.
5
Pressthe
DRILL/TEST
[review]switch.The RED
ALARMLEDof
the
firsl IDC
input
zoneonthe
LSS4
will
illuminate,as
willthe
yellow
trouble
LEDsof
eachNAC
output
circuitand the
yellow
trouble
LEDsof
each
zone
whose
relay
thisIDC
zone
activates.
6 Use the
RESET
[increment]
switchto
stepto
eachIDC
input
zone
installedin the
system,and
reviewthe
NACsand
relays
activatedby
eachIDC
zone.
7
Pressthe
TROUBLE
SILENCE
[incrementto
previous
menu]
switch
to
returntothe
main
(levelO)
menu.
8
Pressthe
RESET
[increment]sw
inchto
steptothe
"configureNAC
output
zone"
menu
i.e.S U
PERV
ISORYLEDON,anda2inthe
display.
9 Use the
RESET
[increment}
switchto
stepto
eachNAC
output
zone
installedin the
systemand
verifythe
display
code.
10Pressthe
TROUBLE
SILENCE
{incrementtoprevious
menu]
switch
to
returntothe
main
(level0)
menu.
II
Pressthe
RESET
[increment]
switchto
returntothe
”assign
relay
”menuas
indicatedby the
TROUBLELEDONanda3inthe
display.
12
Pressthe
DRILLr'TEST
[review]
switch.The RED
ALARMLEDof
the
first IDC
input
zoneontheLSS4
will
illuminateas
willthe
yellow
trouble
LEDsof
eachNAC
output
circuitand the
yellow
trouble
LEDsof
each
zone
whose
relay
thisIDC
zone
activates.
LSS4
Installation,
Operation,and
Maintenance
Manual