Control/
Function
Reset
Alarm
Silence
Trouble
Silence
Test/Auto
Evacuation
Cancel
Zone
Disconnect
Lamp
Test
Table
4-4:
LSS4
Panel
Control
Functions
Function
Description
Resets
system
program
mode.
System
Operation
and
associated
smoke
detectors.
"Increment"
switch
in
Silences
Notification
Appliance
Circuits
definedas
silenceable
audible
circuitsand
usedasan
Alarm
Acknowledge.
CODE"1"
appearsin
display
window.
Initiating
circuit
LEDson
steady.
Alarmsare
silencedand
resoundedby
pressing
Alarm
Silence,but
previously
acknowledged
alarm
LEDs
will
remain
in the
steady
state
(acknowledged)
rather
then
returnto
theNAC
resound
state
(LEDs
pulsing).
This
is
valuable
when
tracking
alarmsas
they
come
in.
If
Alarm
Silence
is
disabled,
acknowledgments
will
NOT be
allowed
until
Alarm
Silence
is
enabled
.
If
Alarm
CutoW
is
active,an
acknowledgefor
each
non-acknowledged
alarm
will be
performed
automaticallyas
partofthe
Cutoff
Option.
Usedto
turnoW
drill
function.
Puts
panelin
programming
mode
when
held
down
during
powerup.
Silencesthe
system
trouble
buzzer.
CODE"2"
appears
in
display
window.
Toggling
switch
alternately
silences&
resounds
trouble
buzzer.
Whenin
European
mode,a
silenced
trouble
buzzer
will
resoundfor.5
seconds
(in
duration)
every14
seconds.
Activates
Notification
Appliance
Circuits.
System
display
indicates
CODE3
NormalLED
extinguishes.
One man
Test
activatedby
pushing
DRILL/TESTand
appropriate
zone
disconnect
switches
simultaneously.
Canadian
(2-Stage)
Operation:
Stops&
Resets
automatic
evacuation
timer
Disables
associated
zone.
System&
zone
troubleLED
pulse.
NormalLED
extinguishes.
System
buzzer
activates.
Lamp
test
function
illuminates
all
system
LEDsfor3
seconds
after
pushing
alarm&
1roubIe
silence
switches
simultaneously.
Table
4-S:
RMOD
Module
Controls/Functions
Control
Function
Disable
Alarm
Zone1/2
Disconnects
Initiating
Alarm
Circuit
RZ1/2.
Zone
troubleand
LSS4
system
trouble
LEDs
flash,
system
trouble
buzzer
sounds.
Disable
Manual
Zone
Disconnectsthe
manual
release
circuit.
Manual
zone
troubleand
LSS4
system
trouble
LEDs
flash,
system
trouble
buzzer
sounds.
Releasing
Circuits
Normal/Disabled
Disables
solenoid
circuits1 & 2.
Releasing
circuit
troubleand
LSS4
system
trouble
LEDs
flash,
system
trouble
buzzer
sounds.
LSS4
Installation,
Operation,and
Maintenance
Manual
4.S