Configuration parameter [BufferFlex] function block
17
5.1.1.3 BufferFlex as a combination tank
Settings - PufferFlex as a combination tank
With a combination tank, you need to set additional
parameters for the hot water treatment.
Explanation of [Switch-on diff.]
Optional: only with combination tank
With a combination tank, this parameter regulates how
far the current warm water temperature can fall before
the hot water tank again demands heat from the boiler.
If the value is set to 15 °C, the current hot water
temperature may drop by 15 °C from the value
[Hot water tank target]. The combination tank does not
demand heat from the boiler unless this happens.
With a combination tank, this value can be set to
approximately 5°C to 8°C if the amount of hot
water is insufficient.
Explanation [Circulation runtime]
Optional: only for circulation pump
This parameter specifies the duration for operating the
circulation pump after it has been started by the control
system. Once this time has expired, the circulation
pump is switched off for the set duration [Circulation
pause].
Example:
[Circulation runtime] = 3 minutes
[Circulation pause] = 10 minutes
If the circulation pump has been started, it is in
operation for 3 minutes and then disabled for
10 minutes. This means that it can only be requested
again by the control system after 13 minutes.
You can determine the required running time of
the circulation pump in the following way. Start
the circulation pump in the control system by means of
manual operation in the inputs and outputs menu. After
starting, measure the time until the fresh water module
warms up the return line for the circulation. This time
(e.g. 3 minutes) is required to heat the hot water pipe.
Then enter this time in parameter [Circulation runtime].
During this time measurement, no hot water may be
tapped (e.g. by sink, shower ...), because otherwise an
incorrect time is measured.
Explanation [Circulation pause]
Optional: only for circulation pump
This parameter sets the pause after a circulation pump
operation. The control system can only restart the
circulation pump after this pause/break has expired.
Example:
[Circulation runtime] = 3 minutes
[Circulation pause] = 10 minutes
If the circulation pump has been started, it is in
operation for 3 minutes and then disabled for
10 minutes. This means that it can only be requested
again by the control system after 13 minutes.
Explanation of [Enable circulation]
Optional: only for circulation pump
This parameter defines the minimum temperature of
the hot water tank for starting the circulation pump. The
circulation pump only starts once the hot water tank
has exceeded this temperature.
Buffer
Hot water area
Switch-on diff.
Circulation
a
a. Only visible with additional circulation pump
Circulation runtime
Circulation pause
Enable circulation

Other manuals for eta T2-BT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the eta T2-BT and is the answer not in the manual?

eta T2-BT Specifications

General IconGeneral
Brandeta
ModelT2-BT
CategoryControl Panel
LanguageEnglish

Related product manuals