Configuration parameter Function block [meter]
35
5.11 Function block [meter]
Parameters to be set
Set or check the following parameters.
Explanation of [Serial no.]
With this parameter, the serial number of the M-bus
meter is entered. This is needed for identification of the
connected M-bus meter (heat flow meter as well as
electric meter), so that the function block can read the
corresponding data of the meter.
If in the serial number are letters, the serial
number must be rotated while entering. Details to
this can be found in the manual of heat flow meter.
example: 1234 0A5678 => 56781234
Explanation of [Read out interval]
The interval for reading out the data of the M-bus meter
is entered with this parameter.
Too short an interval can trigger an error
message on the M-bus meter. Refer to the M-bus
meter operating instructions for the shortest interval to
be set.
Inputs
Heat flow meter
Serial no.
Read out interval
Inputs
Electric meter
Serial no.
Read out interval