12.4. Requirements for connecting cables
CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Ì On the use of other connection components, the requirements in the following table apply.
EUCHNER provides no warranty for safe function in case of failure to comply with these require-
ments.
Observe the following requirements with respect to the connecting cables:
Parameter Value Unit
Conductor cross-section, min. 0.13 mm²
R max. 60 W/km
C max. 120 nF/km
L max. 0.65 mH/km
12.5. Notes on cable laying
Lay all MGB connection cables in a common cable harness.
PLC
+ 24 V DC
cabinet
0 V
MGB-L.-...
FI1A/
FI1B
FO1A/
FO1B
UB 0V UA 0V
Important: lay cables in a common harness
Figure 15: Stipulated cable laying