Euromatic Q81S - Main Power Connection; Start, Stop, and Pedestrian Inputs

Euromatic Q81S
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JP4
JP5
JP6
JP4
JP5
JP6
JP4
JP5 JP6
JP4
JP5 JP6
JP9
230V
6
3.3 START DEVICES
Wire the START contact (N.O. contact) to 1 – 4, terminal JP4.
An additional START contact can be wired in PARALLEL (N.O. contact)
3.4 PEDESTRIAN OPENING
Wire the PEDESTRIAN START (N.O. contact) to 3-4, terminal JP4.
An additional PEDESTRIAN START contact can be wired in PARALLEL
(N.O. contact).
OROLOGIO
3.3.2 KEY SWITCH
Wire the KEY SWITCH (N.O. contact) to 1-4, terminal JP4.
3.2 MAIN POWER
The main line must be protected by a proper CIRCUIT BREAKER.
Connect the line 230V to 18-19-20, terminal JP9, fulfilling the
polarity (18 PHASE – 19 EARTH – 20 NEUTRAL)
CIRCUIT
BREAKER
PHASE
NEUTRAL
PEDESTRIAN
START
3.3.1 TIMER
It is possible to wire a TIMER (N.O. contact) to 1-4, terminal JP4.
ATTENTION!:
when connecting a TIMER, the multi-users function
must be enabled. SW1 DIP 2 = ON