EasyManua.ls Logo

EVAPCO AT Series - Specific Start-Up Steps and Post-Energization Checks

EVAPCO AT Series
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
Operation and Maintenance Instructions
OPTIONAL ACCESSORIES:
6. Coupling/Shaft Inspect flex elements and
hardware for tightness, proper torque &
crack/deterioration monthly
7. Heater Controller Inspect controller and
clean probe ends quarterly
8. Heater Inspect junction box for loose wiring
and moisture one month after start-up and
semi-annually
9. Heater Inspect elements for scale
build-up quarterly
10. Electronic Water Level Controller Inspect
junction box for loose wiring and moisture
semi-annually
11. Electronic Water Level Controller Clean
probe ends of scale build-up quarterly
12. Electronic Water Level Controller –Clean
inside the standpipe annually
13. Solenoid Make-up Valve Inspect and clean
valve of debris as needed
14. Vibration Switch (mechanical) Inspect
enclosure for loose wiring and moisture
one month after start-up and monthly
15. Vibration Switch Adjust the sensitivity
during start-up and annually
16. Sump Sweeper Piping Inspect and clean
piping of debris semi-annually
17. Water Level Indicator Inspect and clean
annually
1. Few Days: Energize motor space heaters
when motor is idle
2. Few Weeks: Run gear reducer for 5 minutes
weekly
3. Several Weeks: Completely fill gear reducer
with oil. Drain to normal level prior to running.
4. One Month or longer: Rotate motor shaft/fan
10 turns bi-weekly
5. One Month or longer: Megger test motor
windings semi-annually
JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
DURING IDLE PERIODS:
MAINTENANCE
CHECKLIST

Table of Contents

Other manuals for EVAPCO AT Series