Do you have a question about the EVAPCO LS Series and is the answer not in the manual?
Adjust float valve for correct water level in the basin.
Verify fan rotation direction and motor current draw.
Confirm pump rotation direction after filling the basin.
This document outlines the rigging and assembly instructions for EVAPCO LS Series Forced Draft Evaporative Condensers and Closed Circuit Coolers. These units are specialized heat transfer products designed for industrial refrigeration and HVAC applications.
The LS Series units are evaporative condensers and closed circuit coolers that facilitate heat transfer by evaporating water, thereby cooling a process fluid or condensing a refrigerant. They are designed for forced draft operation, meaning air is forced through the unit by fans. The units can be shipped either fully assembled (smaller units) or in sections (pan-fan section and coil section) for larger models, requiring on-site assembly. Optional components like discharge hoods, discharge attenuation, and intake attenuation can also be integrated.
Method of Shipment and Rigging: Units are shipped either fully assembled or with the top section(s) separate from the bottom section(s). Mating flanges are designed for a waterproof joint when sealed and bolted. Rigging involves using U-bolts or lift points provided on the pan-fan and coil sections. For extended lifts, safety slings and spreader bars are recommended to prevent damage to upper flanges.
Structural Steel Support: Two structural "I" beams running the length of the unit are required for support, positioned underneath the outer flanges. Mounting holes (19mm diameter) are located in the bottom flange for bolting to the structural steel. Beams should be level to within 1.5mm in 1m. Maximum beam deflection under the unit should be 1/360 of the unit length, not exceeding 13mm, calculated using 55% of the operating weight as a uniform load.
International Building Code (IBC) Provisions: The LS Series Coolers and Condensers are IBC 2006 compliant up to 1g (7kPa wind-load) with standard construction and up to 5.12g (7kPa wind-load) with additional structural modifications. All attached items (piping, ductwork, conduit, electrical connections) must be independently reviewed and isolated to meet applicable wind and seismic loads, requiring flexible attachment to the EVAPCO unit.
Rigging Dimensions (Minimum "H" Dimension for Pan/Fan Section): The minimum "H" dimension (vertical clearance for rigging) varies by unit footprint:
Rigging Dimensions (Minimum "H" Dimension for Coil Section): The minimum "H" dimension for coil sections also varies by unit footprint:
Rigging Dimensions (Minimum "H" Dimension for Complete Unit): For complete units, the minimum "H" dimension is:
Rigging Dimensions (Minimum "H" Dimension for Discharge Hoods/Attenuation and Intake Attenuation): These components share similar "H" dimensions to the coil sections, varying from 2.5m to 5.8m depending on the footprint.
Float Valve Adjustment: Pre-set at the factory, but requires checking after rigging. The float valve should be adjusted so the center of the float is 25mm below the center of the overflow connections when fully closed. Operating pressure range is between 140kPa and 340kPa.
Minimum Operating Level: The minimum operating water level varies by unit footprint:
Assembly Process:
Storage: Units should not be covered with tarps or other coverings if stored before installation to prevent excessive heat buildup and PVC eliminator damage. For extended storage (beyond six months), rotate fan and motor shafts monthly, and purge/regrease fan shaft bearings before start-up.
Freeze Protection: The simplest method is a remote sump, allowing water to drain back when the pump is off. If a remote sump is not used, pan heaters are available, but external water lines, pump, and piping up to the overflow level must be heat traced and insulated. Pan heaters only prevent freezing when fans are off. Units cannot be operated dry (fans on, pump off) unless the pan is completely drained.
Water Treatment: Proper water treatment is essential. Galvanized equipment should be passivated before startup to avoid white rust. Both spray water and process fluid in the coil must be maintained with a water treatment program for efficient operation and extended service life. EVAPCO's Engineering Bulletin 36 provides information on passivation and white rust, and the Operation and Maintenance Instructions detail recommended water chemistry.
General Maintenance: Regular maintenance is crucial for full performance. Refer to the operation and maintenance instructions supplied with the unit for specific procedures.
| Brand | EVAPCO |
|---|---|
| Model | LS Series |
| Category | Accessories |
| Language | English |
Loading...