LS Se
ies Coolers and Condensers
5
Unit
Footprint
(m)
Minimum
“H”
(m)
2.4 x 5.4 5.8
2.4 x 7.3 7.7
2.4 x 11 11.6
3 x 3.6 4.6
3 x 5.4 5.8
3 x 7.3 7.7
3 x 11 11.6
Table 2 – Minimum “H” Dimension for Pan/Fan Rigging
Applying Sealer
T
ape
Once the bottom section has been set on the supporting steel and bolted in place, wipe the top flanges to remove any dirt or
moisture. Place sealer tape over the mounting hole centerline on the side flanges. Apply two strips of sealer tape, one partially
overlapping the other, on the end flanges.
The sealer tape should overlap on the corners as shown in Figure 7. Do not splice the sealer tape along the end flanges and
preferably not on the side flanges if it can be avoided. Always remove the paper backing from the sealer tape.
For units which have two coil sections, sealer tape must be applied to all internal flanges (Figure 8).
Figure 7 – Proper Sealer Tape Application Figure 8 – Sealer Detail for Center Joint of
Units with Two of More Coil Sections
Rigging the Coil
Secti
on
U-bolts or lift points are provided in the four corners of the coil section for lifting and final positioning (Figure 9). On larger coil
sections which have 2 coils, there are additional lift points on the center (Figure 10). Refer to the certified drawing for the coil
section weight. The end and center eliminator sections should be removed before lifting from the U-bolts or lift points and set back
into place once the rig is complete. See Table 3 for the minimum “H” dimensions for rigging the coil section. NOTE
: Use all of the
U-bolts or lift points provided for lifting.
CAUTION: On units shipped as two separate sections, do not assemble sections and attempt to lift the entire unit. The
U-bolts and lift points are designed to carry only the weight of their individual section.
Unit
Footprint
(m)
Minimum
“H”
(m)
1.2 x 1.8 2.5
1.2 x 2.7 3.1
1.2 x 3.6 4.6
1.2 x 5.4 5.8
1.6 x 3.6 4.6
1.6 x 5.4 5.8
2.4 x 3.6 4.6