LS Series Coolers and Condensers
8
Rigging Complete
U
ni
ts
Units that are shipped with the pan-fan and coil sections assembled can be lifted into final position on the structural steel as a
complete unit. U-bolts or lift points are provided in the coil section below the eliminators for lifting and final positioning (Figure 14).
NOTE
: Use all of the U-bolts or lift points provided for lifting.
Figure 14 – Complete 1.2m Wide Units Figure 15 – Extended Lift Complete Unit
The recommended method for extended lifts is to use slings under the unit as shown in Figure 15. Spreader bars should always be
used between the cables at the top of the section to prevent damage to the upper flanges.
NOTE: The U-bolts or other lifting points should be used for final positioning only and for lifting where no danger exists. If
they are used for extended lifts, safety slings and spreader bars should be provided under the sections as shown.
See Table 4 for the minimum “H” dimensions for rigging the entire unit for both standard and extended lifts.
Table 4 – Minimum “H” Dimension for Complete Unit Rigging
Unit
Footprint
(m)
Minimum
“H”
(m)
1.2 x 1.8 2.5
1.2 x 2.7 3.1