EVCO S.p.A. | EV3 Basic Split | Instruction sheet ver. 1.0 | Code 1043BSE103 | Page 2 of 3 | PT 49/18
5.3 Displaying/deleting the compressor functioning hours
Check that the keypad is not locked.
1.
Touch the DOWN key for 1 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
CH1 view compressor functioning hours (days)
CH2 view compressor 2 functioning hours (days) (if u1c... u5c = 1)
rCH delete compressor and compressor 2 functioning hours
3.
Touch the SET key.
4.
Touch the UP or DOWN key to set 149” (to select rCH).
5.
Touch the SET key.
6.
Touch the ON/STAND-BY key (or take no action for 60 s) to exit
the procedure.
5.4 Viewing the temperature detected by the probes
Check that the keypad is not locked.
1.
Touch the DOWN key for 1 s.
2.
Touch the UP or DOWN key within 15 s to select a label.
LAB. DESCRIPTION
Pb1
cabinet temperature (if P4 = 0, 1, 2 or 4)
incoming air temperature (if P4 = 3)
Pb2 evaporator temperature (if P3 = 1 or 2)
Pb3 auxiliary temperature (if P4 = 1, 2, 3 or 4)
Pb4 calculated product temperature (CPT; if P4 = 3)
3.
Touch the SET key.
4.
Touch the ON/STAND-BY key (or take no action for 60 s) to exit
the procedure.
6 SETTINGS
6.1 Setting configuration parameters
1.
Touch the SET key for 4 s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15 s to set the PAS value (de-
fault “-19”).
4.
Touch the SET key (or take no action for 15 s): the display will
show the label “SP”.
5.
Touch the UP or DOWN key to select a parameter.
6.
Touch the SET key.
7.
Touch the UP or DOWN key within 15 s to set the value.
8.
Touch the SET key (or take no action for 15 s).
9.
Touch the SET key for 4 s (or take no action for 60 s) to exit the
procedure.
6.2 Setting the date, time and day of the week (if the EVIF25TBX, EVIF25TWX or
EVIF23TSX module is connected)
N.B.
- do not disconnect the device from the mains in the two minutes after setting the
date, time and day of the week
- if the device communicates with the EVconnect app or the EPoCA remote monitor-
ing system, the date, time and day of the week will be automatically set by the
smartphone or tablet.
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select the label “rtc”.
3.
Touch the SET key: the display will show the label yyfollowed
by the last two figures of the year.
4.
Touch the UP or DOWN key within 15 s to set the year.
5. Repeat actions 3 and 4 to set the next labels.
LAB. MEANING OF THE NUMBERS FOLLOWING THE LABEL
n month (01… 12)
d day (01… 31)
h hour (00… 23)
n minutes (00… 59)
6.
Touch the SET key: the display will show the label for the day of
the week.
7.
Touch the UP or DOWN key within 15 s to set the day of the
week.
LAB. DESCRIPTION
Mon Monday
tuE Tuesday
UEd Wednesday
thu Thursday
Fri Friday
Sat Saturday
Sun Sunday
8.
Touch the SET key: the device will exit the procedure.
9.
Touch the ON/STAND-BY key to exit the procedure beforehand.
6.3 Restoring factory (default) settings and saving customised settings
N.B.
- check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
- saving customised settings overwrites the factory settings.
1.
Touch the SET key for 4 s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15 s to set the value.
VAL. MEANING
149 value for restoring the factory information (default)
161 value for saving customised settings
4.
Touch the SET key (or take no action for 15 s): the display will
show the label dEF(for setting the 149value) or the label
MAP” (for setting the “161” value).
5.
Touch the SET key.
6.
Touch the UP or DOWN key within 15 s to set “4”.
7.
Touch the SET key (or take no action for 15 s): the display will
show - - -flashing for 4 s, after which the device will exit the
procedure.
8. Disconnect the device from the power supply.
9.
Touch the SET key for 2 s before action 6 to exit the procedure
beforehand.
7 CONFIGURATION PARAMETERS
N.B.
- parameters having column "PAR." in grey are not available for EV3SB22
- parameters having column "DEF." in grey are only available for EV3SB54.
NO.
PAR. DEF. SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
NO.
PAR. DEF. ANALOGUE INPUTS MIN... MAX.
2
CA1
0.0
cabinet probe offset
-25... 25 °C/°F
if P4 = 3, incoming air probe
offset
3 CA2 0.0 evaporator probe offset -25... 25 °C/°F
4 CA3 0.0 auxiliary probe offset -25... 25 °C/°F
5 P0 1 type of probe 0 = PTC 1 = NTC
6 P1 1 enable decimal point °C 0 = no 1 = yes
7 P2 0 temperature measurement unit 0 = °C 1 = °F
8
P3
1
evaporator probe function
0 = disabled
1 = defrost + fans
2 = fans
3 = digital input
option 3 only available for
EV3SB22
9
P4
0
configurable input function
0 = digital input
1 = condenser probe
2 = critical temp. probe
3 = outgoing air probe
4 = evaporator probe 2
if P4 = 3, regulation tempera-
ture = product temperature
(CPT)
10
P5
0
value displayed
0 = regulation temperature
1 = setpoint
2 = evaporator temp.
3 = auxiliary temperature
4 = incoming air tempera-
ture
11
P7
50
incoming air effect to calculate
product temperature (CPT)
0... 100 %
CPT = {[(P7 x (incoming air)]
+ [(100 - P7) x
(outgoing air)] : 100}
12
P8 5 display refresh time 0... 250 s: 10
NO.
PAR. DEF. REGULATION MIN... MAX.
13
r0
2.0
setpoint differential
1... 15 °C/°F
if u1c... u5c 1, proportional
band
if Ao1 = 0... 3 or u5c = 0,
band compressor off (relative
to setpoint or setpoint - r0)
14
r1 -40 minimum setpoint -99 °C/°F... r2
15
r2 50.0
maximum setpoint r1... 199 °C/°F
16
r3 0 enable setpoint lock 0 = no 1 = yes
17
r4 0.0 setpoint offset in energy saving 0... 99 °C/°F
18
r5
0
hot or cold mode regulation
0 = cold mode
1 = hot mode
19
r6
0.0
setpoint offset in overcool-
ing/overheating
0... 99 °C/°F
20
r7 0 duration overcooling/overheating 0... 240 min
21
r8
2
DOWN key additional function
0 = disabled
1 = overcooling/overheating
2 = energy saving
22
r12
1
differential position r0
0 = asymmetrical
1 = symmetrical
23
r13
25.0
proportional band modulating
regulation (relative to setpoint)
0... 99 °C/°F
setpoint + r13
for Ao1 = 0... 3 or u5c = 0
24
r14
10
integral action time modulating
regulation
0... 99 min
25
r15
3
type of PWM compressor
1 = Embraco VEM
2 = Embraco VEG
3 = Embraco VNEK and
VNEU
4 = Secop VNL
5 = Secop 33... 133 Hz
not visible if r13 = 0
26
r16
0
percentage 0-10 V output for
compressor with minimum ca-
pacity
0 %... r17
27
r17
100
percentage 0-10 V output for
compressor with maximum ca-
pacity
r6... 100 %
not visible if r13 = 0
28
r18
0
maximum percentage modulating
regulation in energy saving
0... 100 %
0 = disabled
not visible if r13 = 0
NO.
PAR. DEF. COMPRESSOR MIN... MAX.
29
CP0
0
85 Hz PWM compressor time
from power-on
0... 100 s x 10
not visible if r13 = 0
30
CP1
50
percentage 0-10 V compressor
from power-on
0... 100 %
not visible if r13 = 0
31
CP3
100
percentage 0-10 V compressor in
cabinet probe alarm
0... 100 %
not visible if r13 = 0
32
CP4
0
maximum 0-10 V compressor-on
time
0... 240 min
not visible if r13 = 0
33
C0
0
compressor-on delay from
power-on
0... 240 min
34
C1
5
delay between two compressor
switch-ons
0... 240 min
35
C2 3 minimum compressor-off time 0... 240 min
36
C3 0 minimum compressor-on time 0... 240 s
37
C4
10
compressor-off time in cabinet
probe alarm
0... 240 min
38
C5
10
compressor-on time in cabinet
probe alarm
0... 240 min
39
C6
80.0
high condensation signal thresh-
old
0... 199 °C/°F
differential = 2 °C/4 °F
40
C7
90.0
high condensation alarm thresh-
old
0... 199 °C/°F
41
C8 1 high condensation alarm delay 0... 15 min
42
C9
5
cabinet temperature consecutive
time within proportional band to
operate compressor at max.
power
0... 99 h
0 = disabled
until cabinet temperature <
setpoint
43
C10
0
compressor days for mainte-
nance
0... 999 days
0 = disabled
44
C11 10 compressor 2 on delay 0... 240 s
45
C12
2
compressor hour value effect to
balance hours and switch-ons
(BHC)
0... 10
BHC = {[C12 x (compressor
hours)] + [C13 x (compres-
sor switch-ons)]}
46
C13
1
compressor switch-ons value ef-
fect to balance hours and switch-
ons (BHC)
0... 10
BHC = {[C12 x (compressor
hours)] + [C13 x (compres-
sor switch-ons)]}
47
C14
1
constraint between compressors
0 = function of C11
1 = function of r0
2 = function of C12 and C13
NO.
PAR. DEF. DEFROSTING (if r5 = 0) MIN... MAX.
48
d00
0
enable b” mode parameters on
setpoint threshold
0 = no 1 = yes
49
d01
1.0
setpoint threshold to activate “b”
mode parameters
r1... r2
activated if setpoint > d01
50
d0
8
automatic defrost interval
0... 99 h
0 = manual only
if d8 = 3, maximum interval
51
d0b
6
automatic defrost interval “b”
mode
like d0
52
d1
0
type of defrost
0 = electric
1 = hot gas (do not use with
regulation with 2 com-
pressors)
2 = compressor stopped
53
d1b 2 type of defrost “b” mode like d1
54
d2 2.0 defrost end threshold -99... 99 °C/°F
55
d2b 4.0 defrost end threshold “b” mode like d2
56
d3
30
defrost duration
0... 99 min
if P3 = 1, maximum duration
57
d3b 20 defrost duration “b” mode like d3
58
d4 0 enable defrost at power-on 0 = no 1 = yes
59
d5 0 defrost delay from power-on 0... 99 min
60
d6
1
value displayed when defrosting
0 = regulation temperature
1 = locked display
2 = label dEF
61
d7 2 dripping time 0... 15 min
62
d7b 0 dripping time “b” mode like d7
63
d8
0
defrost interval count mode
0 = hours device on
1 = hours compressor on
2 = hours evaporator tem-
perature < d9
3 = adaptive
4 = in real time
64
d9
0.0
evaporation threshold for auto-
matic defrost interval count
-99... 99 °C/°F
65
d11 0 enable defrost timeout alarm 0 = no 1 = yes
66
d15
0
compressor-on consecutive time
for hot gas defrost
-20... 99 min
if values are negative, drip-
ping heaters on time
67
d16
0
pre-dripping time for hot gas de-
frost
0... 99 min
68
d18
40
adaptive defrost interval
0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = manual only
69
d19
3.0
adaptive defrost threshold (rela-
tive to optimal evaporation tem-
perature)
0... 40 °C/°F
optimal evaporation tempera-
ture - d19
70
d20
180
compressor-on consecutive time
for defrost
0... 999 min
0 = disabled
71
d21
200
compressor-on consecutive time
for defrost from power-on and
from overcooling
0... 500 min
if (regulation temperature -
setpoint) > 10°C/20 °F
0 = disabled
72
d22
-2.0
evaporation threshold for adap-
tive defrost interval count (rela-
tive to optimal evaporation tem-
perature)
-10... 10 °C/°F
optimal evaporation tempera-
ture + d22
73
d25
0
enable outgoing air probe for de-
frost in evaporator probe alarm
0 = no 1 = yes
74
d26
6
defrost interval in evaporator
probe alarm
0... 99 h
0 = manual only
if d25 = 1
NO.
PAR. DEF. ALARMS MIN... MAX.
75
A0
0
select value for high/low tem-
perature alarms
0 = regulation temperature
1 = evap. temperature
2 = auxiliary temperature
76
A1 0.0 low temperature alarm threshold -99... 99 °C/°F
77
A2
0
type of low temperature alarm
0 = disabled
1 = relative to setpoint
2 = absolute
78
A4
0.0
high temperature alarm thresh-
old
-99... 99 °C/°F
79
A5
0
type of high temperature alarm
0 = disabled
1 = relative to setpoint
2 = absolute
80
A6
120
high temperature alarm delay
from power-on
0... 240 min
81
A7
15
high/low temperature alarm de-
lay
0... 240 min
82
A8
15
high temperature alarm delay
post-defrosting
0... 240 min
83
A9
15
high temperature alarm delay
from door closure
0... 240 min
84
A10
10
duration of power failure for sav-
ing alarm
0... 240 min
0 = disabled
85
A11
2.0
high/low temperature alarm re-
set differential
1... 15 °C/°F
86
A12
1
type of power failure alarm signal
0 = LED HACCP
1 = LED HACCP + label PF +
buzzer
2 = LED HACCP + label PF +
buzzer (if duration >
A10)
NO.
PAR. DEF. FANS MIN... MAX.
87
F0
1
evaporator fan mode in normal
function
0 = off 1 = on
2 = on if compressor on
3 = thermoregulated (with
regulation temperature
+ F1)
4 = thermoregulated (with
regulation temperature
+ F1) if compressor on
5 = function of F6
6 = thermoregulated (with
F1)
7 = thermoregulated (with
F1) if compressor on
88
F0b
1
evaporator fan mode in normal
function “b” mode
like F0
89
F1
-4.0
evaporator fans regulation
threshold
-99... 99 °C/°F
default -1.0 for EV3SB22
90
F2
0
evaporator fan mode in defrost
and drip mode
0 = off 1 = on
2 = function of F0
default 1 for EV3SB22
91
F2b
0
evaporator fan mode in defrost
and drip mode
like F2
92
F3
2
maximum time evaporator fans
off
0... 15 min
default 0 for EV3SB22
93
F3b
2
maximum time evaporator fans
off
like F3
94
F4
30
time evaporator fans off in en-
ergy saving
0... 240 s x 10
if F0 ≠ 5
95
F5
30
time evaporator fans on in en-
ergy saving
0... 240 s x 10
if F0 ≠ 5
96
F6
0
function for high/low humidity
0 = for low humidity (with
F17 and F18 if compres-
sor off, on if compressor
on)
1 = for high humidity (on)
97
F7
5.0
evaporator fans on threshold
from dripping (relative to set-
point)
-99... 99 °C/°F
setpoint + F7
98
F8
2.0
evaporator fans regulation
threshold differential
1... 15 °C/°F

Questions and Answers: