5.5.2 Description of connectors for EVD HRV
The picture below shows the layout of the EVD HRV connectors.
The tables below describe the EVD HRV connectors.
Connector 1
Part Description
1 relay digital output NO1 (3 A SPST)
2 relay digital output NO 2 (3 A SPST)
3 relay digital outputs CO1/2 (max. 6 A): common
Connector 2
Part Description
1 relay digital output DO3 (12 A SPST): normally open
2 relay digital output DO3 and D04: common
3 relay digital output DO3 and D04: common
4 relay digital output DO4 (8 A SPDT): normally open
5 relay digital output DO4 (8 A SPST): normally closed
7 EVD HRV power supply (115... 230 VAC insulated)
8 EVD HRV power supply (115... 230 VAC insulated)
Connector 3
Part Description
1 Analogue output AO2
2 Analogue output AO1
3 Reference (GND)
4 Dry contact analogue/digital input IN1
5 Dry contact analogue/digital input IN10
6 Dry contact analogue/digital input IN2
7 Dry contact analogue/digital input IN9
8 Dry contact analogue/digital input IN3
9 Dry contact digital input/pulse input IN8
10 Dry contact analogue/digital input IN4