INSTALLATION INSTRUCTIONS
DLAS MODELS
(No Coil Cabinet)
DGAT & DGAM MODELS
(With Built--In Coil Cabinet)
For Installation In:
1. Manufactured (Mobile) Homes
2. Recreational Vehicles & Park
Models
3. Modular Homes & Buildings
SEALED COMBUSTION
DOWNFLOW GAS FURNACES
Forced Draft with Direct Ignition (Hot Surface)
FURNACE SET---UP CHECK LIST
IMPORTANT: ONLY IND I VIDUALS HAVING PROVEN EXPERIENCE WITH THIS TYPE OF EQUIPMENT
SHOULD ATTEMPT TO PERFORM SET-- UP.
- HAS ROOF JACK CROWN B EEN CORRECTLY
INSTALLED?
- HASFURNACEGASVALVEANDBURNERORI-
FICE BEEN CORRECTLY CONVERTED FOR L.P.
GAS WHERE APPLICABLE?
- HASFURNACEGASVALVEBEENDE---RATED
FOR ALTITUD ES ABOVE 2000 FEET WHERE
APPLICABLE?
- IS GAS LINE OUTLET PRES SURE PROPERLY
SET FOR FUEL TYPE? (NATURALGASIS3.5”
W.C.; L.P. IS 10” W.C.)
- IS PRIMARY AIR PROPERLY ADJUSTED PER
INSTALLATION INSTRUCTIONS?
- IS CROSS---OVER DUCT INSTALLED PER
HOME BUILDER AND EVCON INSTALLATION
INSTRUCTIONS?
- HAS FURNACE BEEN OPERATED THROUGH A
COMPLETE HEATING CYCLE?
IMPORTANT: PROPER FURNACE SET--UP AND ADJUSTMENT IS THE RESPONSIBILITY OF THE
RET AILER/HOMEOWNER AND IS NOT COVERED UNDER W ARRANTY.