PARAMETERS CABINETS STAGIONATORE
P. DESCRIPTIONS LISTA
ALARMS
A01 Low temperature alarm differential (relative to SetPoint) -10C°
A02 High temperature alarm differential (relative to SetPoint) 15C°
A03 Temperature alarm delay from switching on card or end of defrost 120 min
A04 High or low temperature delay alarm 60 min
A05 Minimum allowable evaporator temperature for SetPoint -50C°
A06 Maximum permissible temperature of the condenser 50C°
A07 Temperature differential for dirty condenser alarm 60C°
DISPLAY
D01 Unit of temperature (0 Celsius; 1 Fahrenheit) 0
D02 Cell probe offset 0C°
D03 BackLight (0=ON pressing a button; 1=always ON) 0
D06 Locks the display of the temperature during one defrost (0 visualizza;1 nascondi) 0
DEFROST
S01 Type of defrost start 3
1: activates defrost from the keyboard
2: defrosts every S04 hours of refrigerator operation
4: defrosts every S04 hours of compressor operation
8: defrost one hour after switching on refrigerator
16: daily defrosts at hours H01, H02, H03 and H04
128: activates intelligent defrost function
S02 Defrost end temperature 8°C -10°C 30°C 8C°
S03 Maximum duration of one defrost 20 min 1 min 300 min 30 min
S04 Interval between two defrosts 24 H 1 ore 48 ore 6 ore
S05 Type of defrost 1
0: compressor stop
1: heaters
2: reverse compressor cycle with delay time S07
S06 Draining time 180 sec
S07 Compressor start delay for HotGas 0 sec
S08 Compressor operating time for defrost start automatic 5 ore
CONFIGURATION
C01 Microdoor function 1
0: disabled
1: turns off the compressor and evap fan
2: turns off only evap fan
C02 Microdoor polarity 1
C03 Open door max delay 30 min
C04 Enables buzzer (0 disabled; 1 Enabled) 1
C05 Enables starting the relay of Light from the loads menu (0 = disabled; 1 = Enabled) 1
C07 Enables evaporator probe 1
0 disabled
1 evaporator enabled
C08 Function of the condenser probe: (0 disabled; 1 Enabled) 1
C09 Enables the humidity control without probe (0 disabled; 1 Enabled) 1
C10 Enables high pressure digital input (0 disabled; 1 Enabled) 0
C11 High pressure digital input polarity 0
ADJUSTMENT
R01 Hysteresis for SetPoint for adjusting the compressor 3°C 1°C 20°C 3 C°