EasyManua.ls Logo

Exide powerware plus - UPS Startup and Shutdown; Initial Power-on

Exide powerware plus
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Powerware
®
Plus 12 Operator's Manual (164200090 Rev E) !"!&$" "#) 21
4 UPS Startup and Shutdown
The following sections describe the UPS initial powerĆon, system startup, and system
shutdown. Make sure you have completed the installation and configuration of your
UPS before performing these procedures.
Before connecting your protected equipment to the UPS and starting the system, take
a few minutes to identify all controls and indicators on the front panel (see Figure 2 on
page 7).
Initial Power-on
Since the system type is factoryĆset according to your order, it is not mandatory that
you set the type. See the label on the rear of the unit for type information. If you want to
verify or change the system type, perform the following steps:
. Open the top cover of the UPS. Verify that all three breakers input breaker,
battery breaker, and output breaker are in the OFF (O) position.
. Apply AC input power and close(I)theinput breaker in the UPS cabinet.
The front panel indicators come on and then go off. The alarm sounds, indicating
that the battery breaker is open (O). Press the Horn Silence button to turn off the
alarm.
. Press the Menu button to display     &&'%
. Press the down arrow button until    )%& &'# appears.
Press the Select button. The prompt %%("$  appears.
 The default password is MEMORY. It is recommended to change the
default password to ensure security (see page 13). Contact your field
service representative if you have misplaced your password.
. Enter the password by using the up and down arrow buttons to scroll through
the letters; press the right and left arrow buttons to move to other character
positions.
. Press the Select button after entering the password. The display shows
   & )#.
. Press the Select button to display the '&#'& "& option. Figure 4 shows
the unit types and possible configurations provided by the '&#'& "&
option.
 You can press the down arrow button to scroll through all of the menu
options. The selected voltage is indicated with an asterisk (*).
!& )# "%% "!'$&"!% !' &"!%
Low
Voltage
100 VAC
105 VAC
110 VAC
115 VAC
120 VAC
125 VAC
Any of these configurations may be
selected.
    

Related product manuals