EasyManua.ls Logo

Extreme Networks VSP 7254XSQ - Page 17

Extreme Networks VSP 7254XSQ
81 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Task Description
are missing, contact Extreme Networks
support.
7. Make sure that the power cord has the
correct country-specific termination.
See Power cord types and order codes on
page 14.
8. Prepare the rack. Ensure that there is enough rack space to
accommodate a 1RU switch (4.45 cm).
Ensure that the rack is bolted to the floor and
braced if necessary.
Ensure that the rack is grounded to the same
grounding electrode used by the power service
in the area. The ground path must be
permanent and must not exceed 1 Ohm of
resistance from the rack to the grounding
electrode.
March 2020 Installing the VSP 7200 Series 17

Related product manuals