Setting of the maximum correction (Band). The control computer can increase the
setpoint heating until this equals the setpoint house temperature.
Setting of the Delay to minimise the influence of temperature fluctuations.
The control computer only applies the OptiSec-correction, if the actual house
temperature has fallen below the setpoint house temperature during the wait time.
For example, set a wait time of 2 hours. The control computer will only increase the
correction when the actual house temperature has been below the setpoint house
temperature for an uninterrupted period of 2 hours. If the actual house temperature
briefly comes above the setpoint house temperature, the Delay will be reset.
The wait time also applies to the decrease of the corrections. The control computer will
only decrease the correction when the actual house temperature has been above the
setpoint house temperature for an uninterrupted period of 2 hours.
Setting of the time within which the control computer must complete the required
correction increase or decrease.