EasyManua.ls Logo

FATEK FBS-40EA Series - 2.2 Digital and Register Allocations

FATEK FBS-40EA Series
348 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-2
2.2 Digital and Register Allocations
〝*〞is default, user configurable
Typee
Symbol Item Range Remarks
X Digital Input (DI)
X0~X255 (256)
Y Digital Output (DO)
Y0~Y255 (256)
Mapping to external digital I/O
TR Temporary Relay
TR0~TR39 (40)
For branched points
Non-Retentive
M0~M799 (800)*
M1400~M1911 (512)
Internal
Relays
Retentive
M800~M1399 (600)*
M0~M1399 configurable as
Non-retentive or Retentive, M1400~
M1911 are fixed to Non-retentive
M
Special Relay
M1912~M2001 (90)
Non-Retentive
S0~S499 (500)*
S20~ S499 configurable as Retentive
S
Step
Relays
Retentive
S500~S999 (500)*
S500~S999 configurable as Non-retentive
T Timer contact status
T0~T255 (256)
Digital 《 Bit Status 》
C Counter contact status
C0~C255 (256)
0.01STime Base
T0~ T49 (50)*
0.1S Time Base
T50~T199 (150)*
TMR
CV of
Timer
Register
1S Time Base
T200~T255 (56)*
The quantity of
each time base can be configured
Retentive
C0~C139 (140)*
Configurable as Non-retentive
16-bit
Non-Retentivee
C140~C199 (60)*
Configurable as Retentive
Retentive
C200~C239 (40)*
Configurable as Non-retentive
CTR
CV of
Counter
Register
32-bit
Non-Retentive
C240~C255 (16)
Configurable as Retentive
Retentive
R0~R2999 (3000)*
D0~D3999 (4000)
DR
or
HR
Data
Registers
Non-Retentive
R3000~R3839 (840)*
R0~R3839 configurable as
Non-retentive or Retentive,
D0~D3999 are fixed to Retentive
IR Input Registers
R3840~R3903 (64)
Map to external AI Register input
OR Output Registers
R3904~R3967 (64)
Map to external AO /Register output
System Special Registers
R3968~R4167 (200)
D4000~D4095 (96)
High-Spped Timer Register
R4152~R4154 (3)
Hardware (4sets)
DR4096~DR4110
HSC
Registers
Software(4sets)
DR4112~DR4126
Minute Second R4129 R4128
Day Hour R4131 R4130
Year Month R4133 R4132
Special Register
Calendar
Registers
Week R4134
Data Registers
R5000~R8071(3072)*
As general purpose registers if ROR not
been configured.
DR
or
ROR
Read Only Registers
R5000~R8071(0)*
Configurable as ROR for recipe like
application
FR File Registers
F0~F8191(8192)
Need dedicated instruction to access
Register 《 Word Data 》
XR Index Registers
V,Z (2)、 P0~ P9 (10)