IMPORTANT INFORMATION
READ THE FOLLOWING INFORMATION BEFORE INSTALLING:
The contents of this manual are important, and the manual must be kept with the fire alarm control panel
at all times. If building ownership is changed, this manual, including any testing and maintenance information,
must be passed along to the new owner(s).
The fire alarm control panel is part of a system. Manuals and instructions for other devices forming part
of the system should be kept together. Purchasers who install this system for use by others must leave the
instructions with the user. A copy of these instructions is included with each product and is available from the
manufacturer.
This equipment is Listed by various listing agencies for use in fire alarm systems. Use only components which
are compatible with the FCI system. The installation MUST be in accordance with the instructions in this manual.
THEREFORE:
• DO NOT deviate from the procedures described in this manual.
• DO NOT assume any details not shown in the instructions.
• DO NOT modify any electrical or mechanical features.
• DO comply with all codes and standards set forth by the authority having jurisdiction.
The term “Authority Having Jurisdiction” has become a standard term in the fire alarm industry. An acceptable
definition of “Authority Having Jurisdiction” is:
Systems installed in the USA fall under the jurisdiction of some authority. In some areas this may be a local
fire department; in other areas it may be a building inspector, insurance firm, etc. Different authorities may have
their own local requirements for the way the fire alarm system is installed and used. Most local authorities base
their requirements on the NFPA codes, but there may be important differences. You must install this system
in the way in which the authority having jurisdiction requires. If you do not know which authority has jurisdiction
in your area, contact your local fire department or building inspector for guidance.
It is important that you tell users to be aware of any requirements defined by the Authority Having Jurisdiction.
The installation MUST be in accordance with the following standards:
• National Fire Alarm Code (NFPA 72)
• National Electrical Code (NFPA 70)
• Life Safety Code (NFPA 101)
Touching components that are improperly installed, applied or operated could be hazardous and possibly
fatal. Short circuits could cause arcing that could result in molten metal injuries. Therefore, only qualified
technicians familiar with electrical hazards should perform checkout procedures. Safety glasses should be
worn, and test equipment used for voltage measurements should be designed for this purpose and should be
in good working order.
ENVIRONMENTAL CONSIDERATIONS:
It is important that this equipment be operated within its specifications:
Recommended operating temperature range: 60 to 80
o
F (15 to 27
o
C)
Absolute maximum operating temperature range: 32 to 120
o
F (0 to 49
o
C)
Operating humidity: not to exceed 85%,
non-condensing at 90
o
F (32
o
C)
Operating this equipment within the recommended temperature range will extend the useful life of the system
standby batteries.
WARNING - Improper installation, application, or operation can result in death or serious injury.
Page 2 of 28 9000-0007